FAQ No. FAQ00683
Question
I want to input the multi-step speed
command in the Multi-function Input Selection parameter, but Err (error)
is displayed and the signal can’t be input. What is the cause of the
problem and the solution?
Answer
Err (error) will be displayed and it won't
be possible to input the signal if you attempt to input a setting that was
already set with another Multi-function Input selector.
For example, when a multi-step speed command is being used in a 3G3JV
Inverter and you attempt to set n37 (Multi-function Input 2 selector) to 6
(multi-step speed command 1), Err (error) will be displayed and it won't
be possible to input the signal.
This error occurred because n39 (Multi-function Input 4 selector) is set
to its default setting of 6, and this setting was duplicated.
Set n37 (Multi-function Input 2 selector) to 6 after setting another value
in n39 (Multi-function Input 4 selector).