FAQ No. FAQ01345
Question
What is the procedure for setting the pressure of
E8F2 Pressure Sensor
manually?
Answer
Note: Manual setting is possible if
m is selected for the pressure setting method for initial settings.

Use the "Up" and "Down" Keys to change the setting
Note:

1. The pressure setting mode will be entered when the "Set" Key is
pressed, and the OUT1 ON point set to on will be alternately displayed.
2. Use the "Up" and "Down" Keys to change the ON point (OUT1).
3. Press the "Set" Key to select the displayed ON point, and the OUT1 OFF
point set to off will be alternately displayed.
4. Use the "Up" and "Down" Keys to change the OFF point (OUT1).
5. Press the "Set" Key to select the displayed OFF point, and the OUT2 ON
point set to on will be alternately displayed.
6. Use the "Up" and "Down" Keys to change the ON point (OUT2).
7. Press the "Set" Key to select the displayed ON point, and the OUT2 OFF
point set to off will be alternately displayed.
8. Use the "Up" and "Down" Keys to change the OFF point (OUT2).
9. Press the "Set" Key to select the displayed OFF point, and the OUT1 ON
point set to on will be alternately displayed.
Returning to Measurement Mode:
Entering the Settings
Press the "Set" Key for approximately 2 s. (This is effective no matter
what setting is displayed.)
Not Entering the Settings
Press the "Up" and "Down" Keys at the same time. (This is effective no
matter what setting is displayed.)