FAQ No. FAQ01983
Question
Why does the constant-current model sometimes have all indicators ON?
Answer
A constant-current model will sometimes not be able to perform control if
used with a current load much smaller than the rated current.
Possible Countermeasures:
1. Adjust the CUR LIM adjuster until one of the level indicators turns
OFF.

2. If using 50% or less of the rated current, increase the number of turns
of the wire on the CT.
Example:
50% of the rated current: 2 turns
25% of the rated current: 4 turns
Applicable models:
G3PX-2[][]EC/G3PX-2[][]DC Power
Controllers
Other Power Controller
FAQs
What is a level indicator?
What should the minimum load current be set to?
What is the calorific value of the G3PX?
|