Power Controller Topic: Constant-current Model Sometimes Having All Indicators ON

 

FAQ No. FAQ01983

 

Question

Why does the constant-current model sometimes have all indicators ON?
 


Answer

A constant-current model will sometimes not be able to perform control if used with a current load much smaller than the rated current.

Possible Countermeasures:


1. Adjust the CUR LIM adjuster until one of the level indicators turns OFF.

Adjust until one indicator turns OFF

2. If using 50% or less of the rated current, increase the number of turns of the wire on the CT.

Example:
50% of the rated current: 2 turns
25% of the rated current: 4 turns


Applicable models: G3PX-2[][]EC/G3PX-2[][]DC Power Controllers

 

Other Power Controller FAQs

 What is a level indicator?

 What should the minimum load current be set to?

 What is the calorific value of the G3PX?