Power Controller Topic: Calorific Value of G3PX

 

FAQ No. FAQ01994

 

Question

What is the calorific value of the G3PX Power Controllers?
 


Answer

When the G3PX is turned ON and has a load current, residual voltage appears in the switching element. The calculation for calorific value is shown below.


Example:


VRMS (residual voltage) for G3PX-220EUN (rated current 20 A) = 1.6 V (catalog output ON voltage drop) when power consumption is P:


P=20A×1.6V
P=32W
 

This is the power consumption of the G3PX.


To convert to calories:
4.19 W per 1 cal/s

=32W÷4.19

=approx.7.6cal/s


Residual voltage is the voltage loss inside the semiconductor when the semiconductor turns ON.
 

 