Industrial Automation|

Singapore

Sitemap

Contact

OMRON IA Global

 
Select Country

 

View frequently asked questions in your country.

 

   Australia Philippines
   India Singapore
   Indonesia Thailand
   Malaysia
   New Zealand
   Other region

  

Knowledge Library

 

Application Solutions

Technical Guide

FAQs

Case Studies

Downloads

    Catalogs, Manuals,

    CAD Drawing 

 

Frequently Asked Questions

Power Supply Topic: Models that Support Parallel Operation

 

FAQ No. FAQ02011

 

Question

Are there models available that support parallel operation?



Answer

 

The following table shows the models that support parallel connection of outputs as well as the appropriate connection methods.

 

 
Model Connection method
S82K-10024
S8T-DCBU-02
Only connect the +V and -V outputs in parallel
S82K (100 W (- P type only))
S82J (300, 600 W)
Connect the +V and -V outputs in parallel and set the parallel operation
selection switch to PARALLEL.
S8TS (12 V, 24 V) Connect the bus line connector.
S8VM (300, 600, 1,500 W) Connect CB (CN pin 5) and CBG (CN pin 6)
(Use a maximum of 80% of the total output capacity.)

  • Up to two of the same model can be connected in parallel for the S82K (100 W) or S8VM (300 W, 600 W, 1,500 W), up to four of the same model can be connected in parallel for the S8TS and S8T-DCBU-02, and up to five of the same model can be connected for the S82J (300, 600 W).

  • The above table lists the main models for which parallel connection is possible. Refer to the datasheet for each model for details.

  • Attempting parallel connection for models that do not support it may result in an unbalanced load current, possibly causing the rated output current to be exceeded, so the parallel connection is not possible.

  • Use the same length and thickness of load connection line to ensure that the voltage drop between each Power Supply and load is the same.
     

Other Power Supply FAQs

 The output indicator turns ON, but then turns OFF immediately. What is the cause of the problem and solution (in models equipped with the overvoltage protection function)?