FAQ No. FAQ02011
Question
Are there models available that support parallel operation?
Answer
The following table shows the models that
support parallel connection of outputs as well as the appropriate
connection methods.
|
Model |
Connection method |
S82K-10024
S8T-DCBU-02 |
Only connect the +V and -V outputs in parallel |
S82K (100 W (- P type only))
S82J (300, 600 W) |
Connect the +V and -V outputs in parallel and set the parallel operation selection switch to PARALLEL. | |
S8TS (12 V, 24 V) |
Connect the bus line connector. | |
S8VM (300, 600, 1,500 W) |
Connect CB (CN pin 5) and CBG (CN pin 6) (Use a maximum of 80% of the total output capacity.) |
Up to two of the same model can be connected
in parallel for the S82K (100 W) or S8VM (300 W, 600 W, 1,500 W), up to
four of the same model can be connected in parallel for the S8TS and
S8T-DCBU-02, and up to five of the same model can be connected for the
S82J (300, 600 W).
The above table lists the main models for
which parallel connection is possible. Refer to the datasheet for each
model for details.
Attempting parallel connection for models
that do not support it may result in an unbalanced load current, possibly
causing the rated output current to be exceeded, so the parallel
connection is not possible.
Use the same length and thickness of load
connection line to ensure that the voltage drop between each Power Supply
and load is the same.