Page top

Industrial Automation

Industrial Automation

Discontinued On Dec. 2022

SRT2-ID / OD(-1)

Transistor Remote I/O Terminals

SRT2-ID / OD(-1)

Long-distance Communications Supported by SRT2 Models (Long-distance/High-speed Communications Selection)

* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.

Ratings

Inputs

Input current 6 mA max./point
ON delay time 1.5 ms max.
OFF delay time 1.5 ms max.
ON voltage 15 VDC min. between each input terminal and V
OFF voltage 5 VDC max. between each input terminal and V
OFF current 1 mA max.
Insulation method Photocoupler
Input indicators LED (yellow)

Outputs

Rated output current 0.3 A/point
Residual voltage 0.6 V max.
Leakage current 0.1 mA max.
Insulation method Photocoupler
Output indicators LED (yellow)

Characteristics

Communications power supply
voltage
14 to 26.4 VDC
I/O power supply voltage 24 VDC +10%/-15%
I/O power supply current 1 A max.
Current consumption * 50 mA max. at 24 VDC
Connection method Multi-drop method and T-branch method
Connecting Units 4-point and 8-point Terminals: 16 Input Terminals and 16 Output Terminals per
Master
16-point Terminals: 8 Input Terminals and 8 Output Terminals per Master
Dielectric strength 500 VAC for 1 min (1-mA sensing current between insulated circuits)
Noise immunity Conforms to IEC61000-4-4, 2 kV (power lines)
Vibration resistance 10 to 55 Hz, 1.5-mm double amplitude
Shock resistance Malfunction: 200 m/s2
Destruction: 300 m/s2
Mounting strength No damage when 50 N pull load was applied for 10 s in all directions
Terminal strength No damage when 50 N pull load was applied for 10 s
Screw tightening torque 0.6 to 1.18 Nm
Ambient temperature Operating: 0°C to 55°C (with no icing or condensation)
Storage: -20°C to 65°C (with no icing or condensation)
Ambient humidity Operating: 35% to 85%
Weight 4-point and 8-point Terminals: 80 g max.
16-point Terminals: 110 g max.
Approved standards (4/8 points) UL 508, CSA C22.2 No. 14

* The above current consumption is the value with all 4 and 8 and 16 points turned ON excluding the current consumption
   of the external sensor connected to the input Remote Terminal and the current consumption of the load connected to the