NX-series Analog I/O Unit
             
        
last update: October 19, 2020
| Item | Specification | |
|---|---|---|
| Enclosure | Mounted in a panel | |
| Grounding method | Ground to 100 Ω or less | |
| Operating environment | Ambient operating temperature | 0 to 55°C | 
| Ambient operating humidity | 10% to 95% (with no condensation or icing) | |
| Atmosphere | Must be free from corrosive gases. | |
| Ambient storage temperature | -25 to 70°C (with no condensation or icing) | |
| Altitude | 2,000 m max. | |
| Pollution degree | 2 or less: Meets IEC 61010-2-201. | |
| Noise immunity | 2 kV on power supply line (Conforms to IEC61000-4-4.) | |
| Overvoltage category | Category II: Meets IEC 61010-2-201. | |
| EMC immunity level | Zone B | |
| Vibration resistance | Conforms to IEC 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) | |
| Shock resistance | Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions | |
| Applicable standards * | cULus: Listed (UL508), ANSI/ISA 12.12.01, EU: EN 61131-2, C-Tick or RCM, KC Registration, NK, LR | |
* Ask your OMRON representative for the most recent applicable standards for each model.
| Unit name | Analog Input Unit (voltage input type) | Model | NX-AD2603 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Single-ended input | |
| Input range | -10 to +10 V | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±15 V | |||
| Input impedance | 1 MΩ min. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.35 W max. • Connected to a Communi- cations Coupler Unit 1.05 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Not supported. | |||
| Unit name | Analog Input Unit (voltage input type) | Model | NX-AD2604 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | -10 to +10 V | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±15 V | |||
| Input impedance | 1 MΩ min. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.35 W max. • Connected to a Communi- cations Coupler Unit 1.05 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Not supported. | |||
| Unit name | Analog Input Unit (voltage input type) | Model | NX-AD2608 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Selectable Synchronous I/O refreshing or Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | -10 to +10 V | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±15 V | |||
| Input impedance | 1 MΩ min. | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.2% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.35 W max. • Connected to a Communi- cations Coupler Unit 1.05 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Not supported. | |||
| Unit name | Analog Input Unit (voltage input type) | Model | NX-AD3603 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Single-ended input | |
| Input range | -10 to +10 V | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±15 V | |||
| Input impedance | 1 MΩ min. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.35 W max. • Connected to a Communi- cations Coupler Unit 1.10 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Not supported. | |||
| Unit name | Analog Input Unit (voltage input type) | Model | NX-AD3604 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | -10 to +10 V | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±15 V | |||
| Input impedance | 1 MΩ min. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.35 W max. • Connected to a Communi- cations Coupler Unit 1.10 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Not supported. | |||
| Unit name | Analog Input Unit (voltage input type) | Model | NX-AD3608 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Selectable Synchronous I/O refreshing or Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | -10 to +10 V | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±15 V | |||
| Input impedance | 1 MΩ min. | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.2% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.45 W max. • Connected to a Communi- cations Coupler Unit 1.10 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Not supported. | |||
| Unit name | Analog Input Unit (voltage input type) | Model | NX-AD4603 | |
|---|---|---|---|---|
| Number of points | 8 points | External connection terminals | Screwless clamping terminal block (16 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Single-ended input | |
| Input range | -10 to +10 V | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±15 V | |||
| Input impedance | 1 MΩ min. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.45 W max. • Connected to a Communi- cations Coupler Unit 1.15 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Not supported. | |||
| Unit name | Analog Input Unit (voltage input type) | Model | NX-AD4604 | |
|---|---|---|---|---|
| Number of points | 8 points | External connection terminals | Screwless clamping terminal block (16 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | -10 to +10 V | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±15 V | |||
| Input impedance | 1 MΩ min. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.45 W max. • Connected to a Communi- cations Coupler Unit 1.15 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Not supported. | |||
| Unit name | Analog Input Unit (voltage input type) | Model | NX-AD4608 | |
|---|---|---|---|---|
| Number of points | 8 points | External connection terminals | Screwless clamping terminal block (16 terminals) | |
| I/O refreshing method | Selectable Synchronous I/O refreshing or Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | -10 to +10 V | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±15 V | |||
| Input impedance | 1 MΩ min. | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.2% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.45 W max. • Connected to a Communi- cations Coupler Unit 1.15 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Not supported. | |||
| Unit name | Analog Input Unit (current input type) | Model | NX-AD2203 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Single-ended input | |
| Input range | 4 to 20 mA | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±30 mA | |||
| Input impedance | 250 Ω | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.25 W max. • Connected to a Communi- cations Coupler Unit 0.90 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Supported. | |||
| Unit name | Analog Input Unit (current input type) | Model | NX-AD2204 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | 4 to 20 mA | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±30 mA | |||
| Input impedance | 250 Ω | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.25 W max. • Connected to a Communi- cations Coupler Unit 0.90 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Supported. | |||
| Unit name | Analog Input Unit (current input type) | Model | NX-AD2208 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Selectable Synchronous I/O refreshing or Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | 4 to 20 mA | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±30 mA | |||
| Input impedance | 250 Ω | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.2% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.25 W max. • Connected to a Communi- cations Coupler Unit 0.90 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Supported. | |||
| Unit name | Analog Input Unit (current input type) | Model | NX-AD3203 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Single-ended input | |
| Input range | 4 to 20 mA | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±30 mA | |||
| Input impedance | 250 Ω | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.25 W max. • Connected to a Communi- cations Coupler Unit 0.90 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Supported. | |||
| Unit name | Analog Input Unit (current input type) | Model | NX-AD3204 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | 4 to 20 mA | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±30 mA | |||
| Input impedance | 250 Ω | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.25 W max. • Connected to a Communi- cations Coupler Unit 0.90 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Supported. | |||
| Unit name | Analog Input Unit (current input type) | Model | NX-AD3208 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Selectable Synchronous I/O refreshing or Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | 4 to 20 mA | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±30 mA | |||
| Input impedance | 250 Ω | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.2% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.30 W max. • Connected to a Communi- cations Coupler Unit 0.95 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Supported. | |||
| Unit name | Analog Input Unit (current input type) | Model | NX-AD4203 | |
|---|---|---|---|---|
| Number of points | 8 points | External connection terminals | Screwless clamping terminal block (16 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Single-ended input | |
| Input range | 4 to 20 mA | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±30 mA | |||
| Input impedance | 85 Ω | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.40 W max. • Connected to a Communi- cations Coupler Unit 1.05 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Supported. | |||
| Unit name | Analog Input Unit (current input type) | Model | NX-AD4204 | |
|---|---|---|---|---|
| Number of points | 8 points | External connection terminals | Screwless clamping terminal block (16 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | 4 to 20 mA | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±30 mA | |||
| Input impedance | 85 Ω | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.2% (full scale) | ||
| 0 to 55℃ | ±0.4% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.40 W max. • Connected to a Communi- cations Coupler Unit 1.05 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Supported. | |||
| Unit name | Analog Input Unit (current input type) | Model | NX-AD4208 | |
|---|---|---|---|---|
| Number of points | 8 points | External connection terminals | Screwless clamping terminal block (16 terminals) | |
| I/O refreshing method | Selectable Synchronous I/O refreshing or Free-Run refreshing | |||
| Indicator | TS indicator  | Input method | Differential Input | |
| Input range | 4 to 20 mA | |||
| Input conversion range | -5 to 105% (full scale) | |||
| Absolute maximum rating | ±30 mA | |||
| Input impedance | 85 Ω | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.2% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | No supply | Current capacity of I/O power supply terminal | Without I/O power supply terminals | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.45 W max. • Connected to a Communi- cations Coupler Unit 1.10 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |  | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Input disconnection detection | Supported. | |||
| Unit name | Analog Output Unit (voltage output type) | Model | NX-DA2603 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator   | Output range | -10 to +10 V | |
| Output conversion range | -5 to 105% (full scale) | |||
| Allowable load resistance | 5 kΩ min. | |||
| Output impedance | 0.5 Ω max. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.3% (full scale) | ||
| 0 to 55℃ | ±0.5% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.40 W max. • Connected to a Communi- cations Coupler Unit 1.10 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |   | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Unit name | Analog Output Unit (voltage output type) | Model | NX-DA2605 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Selectable Synchronous I/O refreshing or Free-Run refreshing | |||
| Indicator | TS indicator   | Output range | -10 to +10 V | |
| Output conversion range | -5 to 105% (full scale) | |||
| Allowable load resistance | 5 kΩ min. | |||
| Output impedance | 0.5 Ω max. | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.3% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.40 W max. • Connected to a Communi- cations Coupler Unit 1.10 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |   | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Unit name | Analog Output Unit (voltage output type) | Model | NX-DA3603 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator   | Output range | -10 to +10 V | |
| Output conversion range | -5 to 105% (full scale) | |||
| Allowable load resistance | 5 kΩ min. | |||
| Output impedance | 0.5 Ω max. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.3% (full scale) | ||
| 0 to 55℃ | ±0.5% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.35 W max. • Connected to a Communi- cations Coupler Unit 1.25 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |   | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Unit name | Analog Output Unit (voltage output type) | Model | NX-DA3605 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Selectable Synchronous I/O refreshing or Free-Run refreshing | |||
| Indicator | TS indicator   | Output range | -10 to +10 V | |
| Output conversion range | -5 to 105% (full scale) | |||
| Allowable load resistance | 5 kΩ min. | |||
| Output impedance | 0.5 Ω max. | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.3% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 1.60 W max. • Connected to a Communi- cations Coupler Unit 1.25 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |   | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: No restrictions | |||
| Terminal connection diagram |  | |||
| Unit name | Analog Output Unit (current output type) | Model | NX-DA2203 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator   | Output range | 4 to 20 mA | |
| Output conversion range | -5 to 105% (full scale) | |||
| Allowable load resistance | 600 Ω max. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.3% (full scale) | ||
| 0 to 55℃ | ±0.6% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 2.10 W max. • Connected to a Communi- cations Coupler Unit 1.75 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |   | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: For upright installation: No restrictions For any installation other than upright: Restricted as shown in the graph below.   | |||
| Terminal connection diagram |  | |||
| Unit name | Analog Output Unit (current output type) | Model | NX-DA2205 | |
|---|---|---|---|---|
| Number of points | 2 points | External connection terminals | Screwless clamping terminal block (8 terminals) | |
| I/O refreshing method | Selectable Synchronous I/O refreshing or Free-Run refreshing | |||
| Indicator | TS indicator   | Output range | 4 to 20 mA | |
| Output conversion range | -5 to 105% (full scale) | |||
| Allowable load resistance | 600 Ω max. | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.3% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 2.10 W max. • Connected to a Communi- cations Coupler Unit 1.75 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |   | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: For upright installation: No restrictions For any installation other than upright: Restricted as shown in the graph below.   | |||
| Terminal connection diagram |  | |||
| Unit name | Analog Output Unit (current output type) | Model | NX-DA3203 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator   | Output range | 4 to 20 mA | |
| Output conversion range | -5 to 105% (full scale) | |||
| Allowable load resistance | 350 Ω max. | |||
| Resolution | 1/8000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.3% (full scale) | ||
| 0 to 55℃ | ±0.6% (full scale) | |||
| Conversion time | 250 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 2.10 W max. • Connected to a Communi- cations Coupler Unit 1.80 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |   | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: For upright installation: No restrictions For any installation other than upright: Restricted as shown in the graph below.   | |||
| Terminal connection diagram |  | |||
| Unit name | Analog Output Unit (current output type) | Model | NX-DA3205 | |
|---|---|---|---|---|
| Number of points | 4 points | External connection terminals | Screwless clamping terminal block (12 terminals) | |
| I/O refreshing method | Free-Run refreshing | |||
| Indicator | TS indicator   | Output range | 4 to 20 mA | |
| Output conversion range | -5 to 105% (full scale) | |||
| Allowable load resistance | 350 Ω max. | |||
| Resolution | 1/30000 (full scale) | |||
| Overall accuracy | 25℃ | ±0.1% (full scale) | ||
| 0 to 55℃ | ±0.3% (full scale) | |||
| Conversion time | 10 μs/point | |||
| Dimensions | 12 (W) x 100 (H) x 71 (D) | Isolation method | Between the input and the NX bus: Power = Transformer, Signal = Digital isolator (no isolation between inputs) | |
| Insulation resistance | 20 MΩ min. between isolated circuits (at 100 VDC) | Dielectric strength | 510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max. | |
| I/O power supply method | Supply from the NX bus | Current capacity of I/O power supply terminal | IOV: 0.1 A/terminal max., IOG: 0.1 A/terminal max. | |
| NX Unit power consumption | • Connected to a CPU Unit or Communication Control Unit 2.10 W max. • Connected to a Communi- cations Coupler Unit 1.80 W max. | I/O current consumption | No consumption | |
| Weight | 70 g max. | |||
| Circuit layout |   | |||
| Installation orientation and restrictions | Installation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: For upright installation: No restrictions For any installation other than upright: Restricted as shown in the graph below.   | |||
| Terminal connection diagram |  | |||
Refer to the user's manual for the CPU Unit details on the CPU Units to which NX Units can be connected.
| NX Units | Corresponding unit versions/versions | ||
|---|---|---|---|
| Model | Unit version | CPU Unit | Sysmac Studio | 
| NX-AD[][][][] NX-DA[][][][] | Ver.1.0 | Ver.1.13 | Ver.1.17 | 
| NX Units | Corresponding unit versions/versions | |||
|---|---|---|---|---|
| Model | Unit version | EtherCAT Coupler Unit | CPU Unit or Industrial PC | Sysmac Studio | 
| NX-AD[][][][] NX-DA[][][][] | Ver.1.0 | Ver.1.0 | Ver.1.05 | Ver.1.06 | 
| NX Units | Corresponding unit versions/versions | ||||||
|---|---|---|---|---|---|---|---|
| Model | Unit version | Application with an NJ/NX/NY-series Controller *1 | Application with a CS/CJ/CP-series PLC *2 | ||||
| EtherNet/IP Coupler Unit | CPU Unit or Industrial PC | Sysmac Studio | EtherNet/IP Coupler Unit | Sysmac Studio | NX-IO Configurator *3 | ||
| NX-AD[][][][] NX-DA[][][][] | Ver.1.0 | Ver. 1.2 | Ver. 1.14 | Ver. 1.19 | Ver. 1.0 | Ver. 1.10 | Ver. 1.00 | 
| NX Units | Corresponding unit versions/versions | ||
|---|---|---|---|
| Model | Unit version | Communication Control Unit | Sysmac Studio | 
| NX-AD[][][][] NX-DA[][][][] | Ver.1.0 | Ver.1.00 | Ver.1.24 | 
last update: October 19, 2020