Proximity Sensor DC 3-wire/DC 2-wire
last update: October 2, 2023
Types | Double distance Models | ||||
---|---|---|---|---|---|
Size | M8 | M12 | M18 | M30 | |
Model | E2EQ-X2[]8 | E2EQ-X4[]12 | E2EQ-X8[]18 | E2EQ-X15[]30 | |
Sensing distance | 2 mm±10% | 4 mm±10% | 8 mm±10% | 15 mm±10% | |
Setting distance | 0 to 1.6 mm | 0 to 3.2 mm | 0 to 6.4 mm | 0 to 12 mm | |
Differential travel | 15% max. of sensing distance | ||||
Detectable object | Ferrous metals (For non-ferrous metals, refer to the Engineering Data on Catalog.) | ||||
Standard sensing object (Iron) | 8 × 8 × 1 mm | 12 × 12 × 1 mm | 24 × 24 × 1 mm | 45 × 45 × 1 mm | |
Response frequency *1 | 1,500 Hz | 1,000 Hz | 500 Hz | 250 Hz | |
Power supply voltage | 10 to 30 VDC (including 10% ripple (p-p)), Class 2 | ||||
Current consumption | 1-output models: 16 mA max., 2-output models: 20 mA max. | ||||
Output configuration | B[] Models: PNP open collector, C[] Models: NPN open collector | ||||
Operation mode
(with sensing object approaching) |
1-output models (B1, C1): NO (Normally open),
1-output models (B2, C2): NC (Normally closed) 2-output models (B3, C3): NO+NC (Normally open, Normally closed) |
||||
Control
output |
Load current | M8 size
1-output models: 10 to 30 VDC, Class 2, 200 mA max., (-40 to 70°C), 100 mA max., (70 to 85°C) 2-output models: 10 to 30 VDC, Class 2, 50 mA max. M12, M18, M30 size 1-output models: 10 to 30 VDC, Class 2, 200 mA max., 2-output models:10 to 30 VDC, Class 2, 100 mA max. |
|||
Residual voltage | M8 size
1-output models: 2 V max. (Load current: 200 mA, Cable length: 2 m), 2-output models: 2 V max. (Load current: 50 mA, Cable length: 2 m) M12, M18, M30 size 1-output models: 2 V max. (Load current: 200 mA, Cable length: 2 m), 2-output models: 2 V max. (Load current: 100 mA, Cable length: 2 m) |
||||
Indicator *2 | In the Standard I/O mode (SIO mode): Operation indicator (orange, lit) and
communication indicator (green, not lit) In the IO-Link communication mode (COM mode): Operation indicator (orange, lit) and communication indicator (green, blinking at 1 s intervals) |
||||
Protection circuits | Power supply reverse polarity protection, Surge suppressor, Output short-circuit
protection, Output reverse polarity protection |
||||
Ambient temperature range | Operating/Storage: -40 to 85°C (with no icing or condensation)
Note: The UL temperature rating for M12 Pre-wired Connector Models is -25 to 70°C. |
||||
Ambient humidity range | Operating/Storage: 35% to 95% (with no condensation) | ||||
Temperature influence | ±15% max. of sensing distance at 23°C in the temperature range of -40 to 85°C
±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C |
||||
Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | ||||
Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | ||||
Dielectric strength | 1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case | ||||
Vibration resistance
(destruction) |
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions | ||||
Shock resistance
(destruction) |
M8 size: 500 m/s2 10 times each in X, Y, and Z directions/
M12, M18, M30 size: 1,000 m/s2 10 times each in X, Y, and Z directions |
||||
Degree of protection | Pre-wired Models, Pre-wired Connector Models: IEC 60529:IP67, JIS C 0920 Annex 1:
IP67G *4/Connector Models: IEC 60529 IP67 |
||||
Connection method | Pre-wired Models (Standard cable length: 2 m) and Pre-wired Connector Models
(Standard cable length: 0.3 m), M12 Connector Models |
||||
Weight *3
(packed state) |
Pre-wired | Approx. 85 g | Approx. 95 g | Approx. 170 g | Approx. 240 g |
M12 Pre-wired
Smartclick Connector |
Approx. 55 g | Approx. 70 g | Approx. 105 g | Approx. 170 g | |
Connector | Approx. 40 g | Approx. 55 g | Approx. 85 g | Approx. 160 g | |
Materials | Case | M8 size: Fluororesin coating (Base material: SUS303)/
M12, M18, M30 size: Fluororesin coating (Base material: brass) |
|||
Sensing surface | Fluorine resin | ||||
Clamping nuts | Fluororesin coating (Base material: brass) | ||||
Toothed washers | Zinc-plated iron | ||||
Cable | Vinyl chloride (PVC)
Note: Material of Pre-wired Models and Pre-wired Connector Models. |
||||
Main IO-Link functions *2 | Operation mode switching between NO and NC, self diagnosis enabling, excessive
proximity judgment distance selecting, timer function of the control output and timer time selecting, instability output (IO-Link mode) ON delay timer time selecting function, monitor output, operating hours read-out, readout of the sensor internal temperature, and initial reset |
||||
IO-Link
Commun- ication specifica- tions *2 |
IO-Link
specification |
Ver1.1 | |||
Baud rate | COM2 (38.4 kbps), COM3 (230.4 kbps) | ||||
Data length | PD size: 2 bytes, OD size: 1 byte (M-sequence type: TYPE_2_2) | ||||
Minimum cycle
time |
COM2: 2.3 ms, COM3: 0.4 ms | ||||
Accessories | Instruction manual, Clamping nuts, Toothed washer |
Types | Single distance Models | ||||
---|---|---|---|---|---|
Size | M8 | M12 | M18 | M30 | |
Model | E2EQ-X1R5[]8 | E2EQ-X2[]12 | E2EQ-X5[]18 | E2EQ-X10[]30 | |
Sensing distance | 1.5 mm±10% | 2 mm±10% | 5 mm±10% | 10 mm±10% | |
Setting distance | 0 to 1.2 mm | 0 to 1.6 mm | 0 to 4 mm | 0 to 8 mm | |
Differential travel | 15% max. of sensing distance | ||||
Detectable object | Ferrous metals (For non-ferrous metals, refer to the Engineering Data on Catalog.) | ||||
Standard sensing object (Iron) | 8 × 8 × 1 mm | 12 × 12 × 1 mm | 18 × 18 × 1 mm | 30 × 30 × 1 mm | |
Response frequency *1 | 2,000 Hz | 1,500 Hz | 600 Hz | 400 Hz | |
Power supply voltage | 10 to 30 VDC (including 10% ripple (p-p)), Class 2 | ||||
Current consumption | 1-output models: 16 mA max., 2-output models: 20 mA max. | ||||
Output configuration | B[] Models: PNP open collector, C[] Models: NPN open collector | ||||
Operation mode
(with sensing object approaching) |
1-output models (B1, C1): NO (Normally open),
1-output models (B2, C2): NC (Normally closed) 2-output models (B3, C3): NO+NC (Normally open, Normally closed) |
||||
Control
output |
Load current | M8 size
1-output models: 10 to 30 VDC, Class 2, 200 mA max., (-40 to 70°C), 100 mA max., (70 to 85°C) 2-output models: 10 to 30 VDC, Class 2, 50 mA max. M12, M18, M30 size 1-output models: 10 to 30 VDC, Class 2, 200 mA max., 2-output models:10 to 30 VDC, Class 2, 100 mA max. |
|||
Residual voltage | M8 size
1-output models: 2 V max. (Load current: 200 mA, Cable length: 2 m), 2-output models: 2 V max. (Load current: 50 mA, Cable length: 2 m) M12, M18, M30 size 1-output models: 2 V max. (Load current: 200 mA, Cable length: 2 m), 2-output models: 2 V max. (Load current: 100 mA, Cable length: 2 m) |
||||
Indicator *2 | In the Standard I/O mode (SIO mode): Operation indicator (orange, lit) and
communication indicator (green, not lit) In the IO-Link communication mode (COM mode): Operation indicator (orange, lit) and communication indicator (green, blinking at 1 s intervals) |
||||
Protection circuits | Power supply reverse polarity protection, Surge suppressor, Output short-circuit
protection, Output reverse polarity protection |
||||
Ambient temperature range | Operating/Storage: -40 to 85°C (with no icing or condensation)
Note: The UL temperature rating for M12 Pre-wired Connector Models is -25 to 70°C. |
||||
Ambient humidity range | Operating/Storage: 35% to 95% (with no condensation) | ||||
Temperature influence | ±15% max. of sensing distance at 23°C in the temperature range of -40 to 85°C
±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C |
||||
Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | ||||
Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | ||||
Dielectric strength | 1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case | ||||
Vibration resistance
(destruction) |
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions | ||||
Shock resistance
(destruction) |
M8 size: 500 m/s2 10 times each in X, Y, and Z directions/
M12, M18, M30 size: 1,000 m/s2 10 times each in X, Y, and Z directions |
||||
Degree of protection | Pre-wired Models, Pre-wired Connector Models: IEC 60529:IP67, JIS C 0920 Annex 1:
IP67G *4/Connector Models: IEC 60529 IP67 |
||||
Connection method | Pre-wired Models (Standard cable length: 2 m) and Pre-wired Connector Models
(Standard cable length: 0.3 m), M12 Connector Models |
||||
Weight *3
(packed state) |
Pre-wired | Approx. 85 g | Approx. 95 g | Approx. 170 g | Approx. 240 g |
M12 Pre-wired
Smartclick Connector |
Approx. 55 g | Approx. 70 g | Approx. 105 g | Approx. 170 g | |
Connector | Approx. 40 g | Approx. 55 g | Approx. 85 g | Approx. 160 g | |
Materials | Case | M8 size: Fluororesin coating (Base material: SUS303)/
M12, M18, M30 size: Fluororesin coating (Base material: brass) |
|||
Sensing surface | Fluorine resin | ||||
Clamping nuts | Fluororesin coating (Base material: brass) | ||||
Toothed washers | Zinc-plated iron | ||||
Cable | Vinyl chloride (PVC)
Note: Material of Pre-wired Models and Pre-wired Connector Models. |
||||
Main IO-Link functions *2 | Operation mode switching between NO and NC, self diagnosis enabling, excessive
proximity judgment distance selecting, timer function of the control output and timer time selecting, instability output (IO-Link mode) ON delay timer time selecting function, monitor output, operating hours read-out, readout of the sensor internal temperature, and initial reset |
||||
IO-Link
Commun- ication specifica- tions *2 |
IO-Link
specification |
Ver1.1 | |||
Baud rate | COM2 (38.4 kbps), COM3 (230.4 kbps) | ||||
Data length | PD size: 2 bytes, OD size: 1 byte (M-sequence type: TYPE_2_2) | ||||
Minimum cycle
time |
COM2: 2.3 ms, COM3: 0.4 ms | ||||
Accessories | Instruction manual, Clamping nuts, Toothed washer |
Size | M12 | M18 | M30 | |
---|---|---|---|---|
Model | E2EQ-X4D[]12 | E2EQ-X8D[]18 | E2EQ-X15D[]30 | |
Sensing distance | 4 mm ±10% | 8 mm ±10% | 15 mm ±10% | |
Setting distance *1 | 0 to 3.2 mm | 0 to 6.4 mm | 0 to 12 mm | |
Differential travel | 15% max. of sensing distance | |||
Detectable object | Ferrous metals (For non-ferrous metals, refer to Engineering Data on Catalog.) | |||
Standard sensing object (Iron) | 12 × 12 × 1 mm | 18 × 18 × 1 mm | 30 × 30 × 1 mm | |
Response frequency *2 | 1,000 Hz | 500 Hz | 250 Hz | |
Power supply voltage | 10 to 30 VDC (including 10% ripple (p-p)), Class 2 | |||
Current consumption | 0.8 mA max. | |||
Control
output |
Load current | 3 to 100 mA | ||
Residual voltage | 5 V max. (Load current: 100 mA, Cable length: 2 m) | |||
Indicator | Operation indicator (orange), Setting indicator (green) | |||
Operation mode | NO
Refer to the timing charts under I/O Circuit Diagrams/Timing charts on Catalog for details. |
|||
Protection circuits | Surge suppressor, Load short-circuit protection | |||
Ambient temperature range | Operating: -25 to 70°C, Storage: -40 to 85°C (with no icing or condensation) | |||
Ambient humidity range | Operating and Storage: 35% to 95% (with no condensation) | |||
Temperature influence | ±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C | |||
Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | |||
Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | |||
Dielectric strength | 1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case | |||
Vibration resistance (destruction) | 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions | |||
Shock resistance (destruction) | 1,000 m/s2 10 times each in X, Y, and Z directions | |||
Degree of protection | Pre-wired Models, Pre-wired Connector Models: IEC 60529:IP67, JIS C 0920 Annex
1: IP67G |
|||
Connection method | Pre-wired Models (Standard cable length: 2 m) and
M12 Pre-wired Smartclick Connector Models (Standard cable length: 0.3 m) |
|||
Weight
(packed state) |
Pre-wired | Approx. 100 g | Approx. 180 g | Approx. 250 g |
M12 Pre-wired
Smartclick Connector |
Approx. 75 g | Approx. 110 g | Approx. 180 g | |
Materials | Materials | Fluororesin coating (Base material: brass) | ||
Sensing surface | Fluororesin | |||
Clamping nuts | Fluororesin coating (Base material: brass) | |||
Toothed washer | Zinc-plated iron | |||
Cable | Vinyl chloride (PVC) | |||
Accessories | Instruction manual, Clamping nuts, Toothed washer |
Size | M8 | M12 | M18 | M30 | |
---|---|---|---|---|---|
Model | E2EQ-X3[]8 | E2EQ-X6[]12 | E2EQ-X12[]18 | E2EQ-X22[]30 | |
Sensing distance | 3 mm±10% | 6 mm±10% | 12 mm±10% | 22 mm±10% | |
Setting distance | 0 to 2.4 mm | 0 to 4.8 mm | 0 to 9.6 mm | 0 to 16.8 mm | |
Differential travel | 15% max. of sensing distance | ||||
Detectable object | Ferrous metals (For non-ferrous metals, refer to the Engineering Data on Catalog.) | ||||
Standard sensing object (Iron) | 9 × 9 × 1 mm | 18 × 18 × 1 mm | 36 × 36 × 1 mm | 66 × 66 × 1 mm | |
Response frequency *1 | 1,000 Hz | 800 Hz | 500 Hz | 200 Hz | |
Power supply voltage | 10 to 30 VDC (including 10% ripple (p-p)), Class 2 | ||||
Current consumption | 1-output models:
16 mA max. |
1-output models: 16 mA max., 2-output models: 20 mA max. | |||
Output configuration | B[] Models: PNP open collector, C[] Models: NPN open collector | ||||
Operation mode
(with sensing object approaching) |
1-output models (B1,
C1): NO (Normally open), 1-output models (B2, C2): NC (Normally closed) |
1-output models (B1, C1): NO (Normally open),
1-output models (B2, C2): NC (Normally closed), 2-output models (B3, C3): NO+NC (Normally open, Normally closed) |
|||
Control
output |
Load current | 1-output models: 10 to
30 VDC, Class 2, 100 mA max. |
1-output models: 10 to 30 VDC, Class 2, 100 mA max.,,
2-output models: 10 to 30 VDC, Class 2, 50 mA max. |
||
Residual voltage | 1-output models: 2 V
max. (Load current: 100 mA, Cable length: 2 m) |
1-output models: 2 V max. (Load current: 100 mA, Cable
length: 2 m), 2-output models: 2 V max. (Load current: 50 mA, Cable length: 2 m) |
|||
Indicator *2 | In the Standard I/O mode (SIO mode): Operation indicator (orange, lit) and
communication indicator (green, not lit) In the IO-Link communication mode (COM mode): Operation indicator (orange, lit) and communication indicator (green, blinking at 1 s intervals) |
||||
Protection circuits | Power supply reverse polarity protection, Surge suppressor, Output short-circuit
protection, Output reverse polarity protection |
||||
Ambient temperature range | Operating/Storage: -25 to 70°C (with no icing or condensation) | ||||
Ambient humidity range | Operating/Storage: 35% to 95% (with no condensation) | ||||
Temperature influence | ±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C | ||||
Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | ||||
Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | ||||
Dielectric strength | 1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case | ||||
Vibration resistance
(destruction) |
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions | ||||
Shock resistance
(destruction) |
500 m/s2 10 times
each in X, Y, and Z directions |
1,000 m/s2 10 times each in X, Y, and Z directions | |||
Degree of protection | Pre-wired Models, Pre-wired Connector Models: IEC 60529: IP67, JIS C 0920 Annex 1:
IP67G *4 Connector Models: IEC 60529: IP67 |
||||
Connection method | Pre-wired Models (Standard cable length: 2 m) and Pre-wired Connector Models
(Standard cable length: 0.3 m), M12 Connector Models |
||||
Weight *3
(packed state) |
Pre-wired | Approx. 85 g | Approx. 95 g | Approx. 180 g | Approx. 260 g |
M12 Pre-wired
Smartclick Connector |
Approx. 55 g | Approx. 70 g | Approx. 115 g | Approx. 200 g | |
Connector | Approx. 40 g | Approx. 55 g | Approx. 95 g | Approx. 180 g | |
Materials | Case | Fluororesin coating (Base material: brass) | |||
Sensing surface | Fluorine resin | ||||
Clamping nuts | Fluororesin coating (Base material: brass) | ||||
Toothed washers | Zinc-plated iron | ||||
Cable | Vinyl chloride (PVC)
Note: Material of Pre-wired Models and Pre-wired Connector Models. |
||||
Main IO-Link functions *2 | Operation mode switching between NO and NC, self diagnosis enabling, excessive
proximity judgment distance selecting, timer function of the control output and timer time selecting, instability output (IO-Link mode) ON delay timer time selecting function, monitor output, operating hours read-out, readout of the sensor internal temperature, and initial reset |
||||
IO-Link
Commun- ication specifica- tions *2 |
IO-Link
specification |
Ver 1.1 | |||
Baud rate | COM2 (38.4 kbps), COM3 (230.4 kbps) | ||||
Data length | PD size: 2 bytes, OD size: 1 byte (M-sequence type: TYPE_2_2) | ||||
Minimum cycle
time |
COM2: 2.3 ms, COM3: 0.4 ms | ||||
Accessories | Instruction manual, Clamping nuts, Toothed washer |
Size | M8 | M12 | M18 | M30 | |
---|---|---|---|---|---|
Model | E2EQ-X3D[] | E2EQ-X7D[] | E2EQ-X11D[] | E2EQ-X20D[] | |
Sensing distance | 3 mm ±10% | 7 mm ±10% | 11 mm ±10% | 20 mm ±10% | |
Setting distance *1 | 0 to 2.4 mm | 0 to 4.9 mm | 0 to 8.8 mm | 0 to 16 mm | |
Differential travel | 15% max. of sensing distance | ||||
Detectable object | Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to
Engineering Data on Catalog.) |
||||
Standard sensing object
(Iron) |
9 × 9 × 1 mm | 21 × 21 × 1 mm | 33 × 33 × 1 mm | 60 × 60 × 1 mm | |
Response frequency *2 | 250 Hz | 250 Hz | 250 Hz | 200 Hz | |
Power supply voltage | 10 to 30 VDC, (including 10% ripple (p-p)) | ||||
Leakage current | 0.8 mA max. | ||||
Control
output |
Load current | 3 to 100 mA | |||
Residual
voltage |
Polarity: 3 V max. (Load current: 100 mA, Cable length: 2 m)
No polarity: 5 V max. (Load current: 100 mA, Cable length: 2 m) |
||||
Indicator | D1 Models: Operation indicator (orange), Setting indicator (green)
D2 Models: Operation indicator (orange) |
||||
Operation mode | D1 Models: NO
D2 Models: NC Refer to the timing charts under I/O Circuit Diagrams/Timing charts on Catalog for details. |
||||
Protection circuits | Surge suppressor, Load short-circuit protection | ||||
Ambient temperature
range |
Operating: -25 to 70°C, Storage: -40 to 85°C (with no icing or condensation) | ||||
Ambient humidity range | Operating and Storage: 35% to 95% (with no condensation) | ||||
Temperature influence | ±10% max. of sensing distance at 23°C
in the temperature range of -25 to 70°C |
±20% max. of sensing distance at 23°C
in the temperature range of -25 to 70°C |
|||
Voltage influence | ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range | ||||
Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | ||||
Dielectric strength | 1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case | ||||
Vibration resistance
(destruction) |
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions | ||||
Shock resistance
(destruction) |
500 m/s2 10 times
each in X, Y, and Z directions |
1,000 m/s2 10 times each in X, Y, and Z directions | |||
Degree of protection | Pre-wired/Pre-wired M12 Connector: IP67 (IEC 60529) and IP67G *3 (JIS C 0920 Annex 1) | ||||
Connecting method | Pre-wired (Standard cable length: 2 m) and Pre-wired M12 Connector (Standard cable
length: 0.3 m) |
||||
Weight
(packed state) |
Pre-wired
Models |
Approx. 60 g | Approx. 70 g | Approx. 150 g | Approx. 210 g |
Pre-wired
M12 Connector |
Approx. 30 g | Approx. 40 g | Approx. 90 g | Approx. 140 g | |
Materials | Case | Fluororesin coating (Base material: brass) | |||
Sensing
surface |
Fluororesin | ||||
Clamping
nuts |
Fluororesin coating (Base material: brass) | ||||
Toothed
washer |
Zinc-plated iron | ||||
Cable | Vinyl chloride (PVC) | ||||
Accessories | Instruction manual, Clamping nuts, Toothed washer |
last update: October 2, 2023