PLC Series |
CS Series |
CJ Series |
|
Size (Height) |
130 mm |
90 mm |
|
Unit Name |
Loop Control Board |
Loop Control Unit |
Process-control CPU Unit |
Loop-control CPU Unit |
|
Model |
CS1W-LCB01/05 |
CS1W-LC001 |
CS1D-CPU[][]P |
CJ1G-CPU[][]P |
|
Appearance |
 |
 |
![CS1D-CPU[][]P Process Control CPU Unit](pic03.jpg) |
![CJ1G-CPU[][]P Loop Control CPU Unit](pic04.jpg) |
|
Unit
Classification |
Inner Board |
CPU Bus Unit |
Process-control CPU Unit
(CS1D-CPU[][]H and Loop Control Board set) |
CJ1 CPU Unit Built-in Loop Control
Board |
|
Compatible CPU
Unit |
CS1[]-CPU[][]H or
CS1[]-CPU[][]S |
CS1[]-CPU[][]H or
CS1D-CPU[][]S or
CS1D-CPU[][]H |
Built-in Loop Control Function in
CS1D CPU Unit |
Built-in Loop Control Function in
CS1G CPU Unit |
|
Duplex Mode |
Not supported |
Not supported |
Supported |
Not supported |
|
Number of
Function Blocks |
Control Block +
Operation Block:
LCB01: 50 blocks max.
LCB05: 500 blocks max.
• Fuzzy Logic <Block Model 016>
• Arithmetic Operation <Block Model
126>
• Time Sequence Data Statistics <Block Model 153>: 100 Blocks
max.
|
Control Block: 32
Operation Block: 249 |
Control Block +
Operation Block:
500 blocks max.
However, external automatic
controller block (ES100X Controller Terminal Block <Block
Model 045>) cannot be used.
• Fuzzy Logic (Block Model 016)
• Arithmetic Operation <Block Model
126>
• Time Sequence Data Statistics <Block Model 153>: 100 Blocks
max. |
Control Block +
Operation Block:
CJ1W-CPU42P:
50 blocks max.
CJ1W-CPU43/44/45P:
300 blocks max
However, external automatic
controller block (ES100X Controller Terminal Block
<Block Model 045>) cannot be used.
• Fuzzy Logic (Block Model 016)
• Arithmetic Operation <Block
Model 126>
• Time Sequence Data Statistics <Block Model 153>: 100
Blocks max.
|
|
Sequence Control |
Step Ladder or Sequence Table
(Cannot be used simultaneously)
(Note: The CS1W-LCB01 supports step
ladder programming only)
|
Step Ladder |
Step Ladder or Sequence Table
(Cannot be used simultaneously) |
Step Ladder |
|
Communication
with ES100X Controller |
ES100X Controller
Terminal Block |
ES100X Controller
Terminal Block |
Not Supported |
Not Supported |
|
User Link Table Function |
Supported |
None (Expanded CPU Unit Terminals
are used) |
Supported |
Supported |
|
Main Function
Operation Cycle |
10, 20, 50, 100, 200, 500, 1000,
2000ms |
100, 200, 500, 1000, 2000ms |
100, 200, 500, 1000, 2000ms |
10, 20, 50, 100, 200, 500, 1000,
2000ms |
|
Speed of Data Exchange with CPU Unit |
Operation
Cycle |
1 Cycle Time + Operation Cycle |
Refreshing
split over multiple CPU Unit cycles during Board operation cycle |
Operation Cycle |
|
CPU Unit Cycle
Time Restrictions |
None |
None |
Must be 1/5
the shortest operation cycle or less. |
None |
|
Max. Delay Before Hot Start |
Up to 24
hours after power is turn OFF (at an ambient temperature of 25°C) |
Up to one
year after power is turned OFF. |
Up to 24
hours after power is turn OFF (at an ambient temperature of 25°C) |
Up to 5
minutes after power is turn OFF (at an ambient temperature of
25°C) |
|
RAM Backup Method |
Super Capacitor |
Battery, Super Capacitor |
Super Capacitor |
Super Capacitor (Super capacitor is
backed up by Battery in CPU Unit.) |