Item
Model |
G2AK
Latching Type |
MK-I/-S |
G7T I/O |
G2RS |
|
Appearance |
 |
 |
 |
 |
|
Features |
Magnetic
latching version of G2A ideal
for sequence control.
|
Exceptionally reliable
general-purpose relay
features mechanical
indicator/test
button.
|
These
super-slim relays each
measure
only 29 x 10 x 32 mm
(W x D x
H) and come in AC
and DC
input models as well as SPST-NO
and SPST-NC output
models. |
Reliable
and unique test button models now available. High
switching power (1 pole: 10 A). Highly
functional socket also available.
|
|
Contact Ratings |
Contact form |
DPDT |
DPDT/3PDT |
SPST-NO, SPST-NC, SPDT |
SPST-NO |
SPDT |
DPDT |
|
Mechanism |
Bifurcated
|
Single |
Input: Bifurcated crossbar
Output: Single |
Bifurcated
|
Single |
Bifur-cated |
Single |
|
Material |
Movable: Au-clad+Ag
Stationary: Ag/Pd |
Ag |
Input: AgAu+Ag
Output: AgSnIn |
Ag-alloy |
|
Rated Load *
(Resistive Load) |
0.3 A at 110 VAC, 5,000,000 operations min.
0.5 A at 24 VDC, 5,000,000 operations min. |
10 A (NO),
5 A (NC) at
250 VAC/28
VDC |
Input: 1 A
at 24 VDC, 50,000 operations min.
10 mA at
24 VDC, 10,000,000 operations min.
Output: 5
A at 24 VDC, 1,000,000 operations min. |
1A at
250 VAC/ 30 VDC |
10A at
250 VAC/ 30 VDC |
1A at
250 VAC/ 30 VDC |
5 A at
250 VAC/30 VDC |
|
Maximum switched
current |
AC: 1A
DC: 3A |
10A |
Input: 1A
Output: 5A |
1A |
10A |
1A |
5A |
|
Failure rate
(reference value) |
1 mA at 100 m VDC |
10 mA at 1 VDC |
Input: 100
µA at 1 VDC
Output: 10
mA at 5 VDC |
1 mA at 5 VDC |
100 mA at 5 VDC |
1 mA at 5 VDC |
10 mA at 5 VDC |
|
Coil Ratings |
Rated Voltage |
6 to 48 VDC
6 to 100
VAC |
6 to 125
VDC;
6 to
200/220 VAC |
110/120
VAC,
220/240
VAC,
12 VDC, 24
VDC 100/110 VDC |
5 to
100 VDC
12 to
240 VAC |
|
Power consumption
(approx.) |
Set: 2 to 2.2 W (DC); 1.6 to 2 VA (AC)
Reset: 1 to 1.2 W (DC); 0.5 to 1.2 VA (AC)
|
1.5 W (DC)
2.3 to 2.7
VA (AC)
|
0.7 VA
(AC)
0.5 W (DC) |
0.53 W (DC)
0.7 to 0.9 VA (AC)
|
|
Endurance |
Mechanical |
5 x 10 6 |
5 x 10 6 |
50 x 10 6 |
10 x 10 6
(AC), 20 x 106
(DC) |
|
Electrical |
5,000 x 10³ |
500 x 10³ |
Input: 500 x 10³
Output: 1,000 x 10³ |
100 x 10³ |
|
Dielectric Strength |
Between coil and
contacts |
1,500 VAC
for 1 min. |
2,000 VAC
for 1 min. |
2,000 VAC
for 1 min. |
5,000 VAC
for 1 min. |
|
Between contacts of
different polarities |
1,500 VAC
for 1 min. |
2,000 VAC
for 1 min. |
-- |
-- |
3,000 VAC
for 1 min. |
|
Between contacts of
same polarity |
700 VAC
for 1 min. |
1,000 VAC
for 1 min. |
1,000 VAC
for 1 min. |
1,000 VAC
for 1 min. |
|
Between set and
reset coil |
1,000 VAC
for 1 min. |
-- |
-- |
--- |
--- |
|
Ambient temperature |
–10°C to
40°C |
–10°C to
40°C |
–40°C to
70°C |
–40°C to
70°C |
|
Function |
• Latching (double binding)
• Arc barriers
• Mechanical indicator
|
• Mechanical indicator |
• • Built-in mechanical operation
indicator
|
• LED
indicator
•
Test
button
•
Built-in diode
|
|
Sealing |
• Cased
(unsealed)
• Fully sealed |
Cased
(unsealed) |
Closed/cased |
Cased
(unsealed) |
|
Terminal
construction ** |
 |
|
|
 |
|
Approved standards |
 |
     |
  |
     |