Control Panel Relays:

   

 

Page 1 of 3 

Next >>

 

 Item                              Model

MY New Model

MY3, MY[]-02, MY[]F

MYK

LY

Appearance

Features

Versatile relay, ideal for power and sequence control applications, meets many other application requirements.

Versatile relay, ideal for power and sequence control applications, meets many other application requirements.

Magnetic latching relay ideal
for memory and data transmission
circuits.

Compact, general-purpose 15-A and 10-A relays ideal for many applications.

Contact Ratings

Contact form

DPDT

4PDT

DPDT

3PDT

4PDT

DPDT

SPDT

DPDT

3DPT

4DPT

Mechanism

Single

Single

Bifur-cated

Single

Single

Single

Bifur-cated

Single

Single

 

Bifur-cated

Single

Material

Ag

Au-clad+Ag

Ag

Ag

Au-Plated+Ag

Au-Plated+Ag

Ag-alloy

Ag

Ag-alloy

Rated Load * (Resistive Load)

5A at 250 VAC/ 30VDC

3A at 250 VAC/ 30 VDC

5A at 220 VAC/24VDC

3A at 220 VAC/24VDC

3A at 220 VAC / 24 VDC

15A at 110 VAC/ 24 VDC

10A at 110 VAC/ 24 VDC

5A at 110 VAC/ 24 VDC

10 A at 110 VAC/24 VDC

Maximum switched current

10A

5A

5A

3A

3A

15A

10A

7A

10A

Failure rate (reference value)

1 mA at 5 VDC

1 mA at 1 VDC

100 µA at 1 VDC

1mA at 5 VDC

1 mA at 1 VDC

100 µA at 1 VDC

1 mA at 1 VDC

100 mA at 5 VDC

10 mA at 5 VDC

100 mA at 5 VDC

Coil Ratings

Rated Voltage

6 to 100/110 VDC

6 to 220/240 VAC

6 to 100/110 VDC

6 to 220/240 VAC

6 to 24 VDC

6 to 100 VAC

6 to 100/110 VDC

6 to 220/240 VAC

Power consumption (approx.)

0.9 W (DC)

0.9 to 1.2 VA (AC)

0.9 W (DC)

0.9 to 1.2 VA (AC)

Set: 1.3 W (DC)

0.6 to 0.9 VA (AC)

Reset: 0.6 W (DC)

0.2 to 0.5 VA (AC)

0.9 W (DC)

0.9 to 1.2 VA (AC)

1.4 W (DC)

1.6 to 2.0

VA (AC)

1.5 W (DC)

1.95 to 2.5

VA (AC)

Endurance

Mechanical

50 x 106 (AC), 100 x 106 (DC)

20 x 106

50 x 106 (AC)

100 x 106 (DC)

20 x 106

100 x 106

50 x 106 (AC), 100 x 106 (DC)

Electrical

500 x 10³

200 x 10³

100 x 10³

500 x

10³

500 x

10³

200 x

10³

100 x

10³

200 x 10³

200 x 10³

500 x 10³

200 x 10³

Dielectric Strength

Between coil and contacts

2,000 VAC for 1 min.

2,000 VAC for 1 min.

1,500 VAC for 1 min.

2,000 VAC for 1 min.

Between contacts of different polarities

2,000 VAC for 1 min.

2,000 VAC for 1 min.

1,500 VAC for 1 min.

--

2,000 VAC for 1 min.

Between contacts of same polarity

1,000 VAC for 1 min.

1,000 VAC for 1 min.

1,000 VAC for 1 min.

1,000 VAC for 1 min.

Between set and reset coil

--

--

1,000 VAC for 1 min.

---

Ambient temperature

–55°C to 70°C

–55°C to 70°C

–55°C to 60°C

–25°C to 55°C

–25°C to 40°C

Function

• Mechanical indicator
• LED indicator
• Built-in diode
• Built-in CR
• Test button
• Arc barriers

• LED indicator
• Built-in diode
• Arc barriers

• • Latching

• • Mechanical indicator

LED indicator

Built-in diode

Built-in CR

Test button

Sealing

Cased (unsealed)

Cased (unsealed)

Cased (unsealed)

Cased (unsealed)

Terminal construction **

Approved standards

--

 

Page 1 of 3 

Next >>

*   Numbers in parentheses apply to cased (unsealed) types.

** denotes PCB terminals, plug-in (octal-pin) terminal, plug-in/solder terminal,

    quick-connect terminal, and screw terminal.