Industrial Automation|

Singapore

Sitemap

Contact

OMRON IA Global

 
Ask the Guru

» Send your questions to our experts!


Subscribe to Omron E-newsletter!

Standards Certification

UL Certification for Wireless / RFID Systems

 

Wireless Components

Code Readers

RFID Systems

 

 

Wireless Components

 

Model

Ratings

File No.

WT30-M01-FLK
WT30-SID16
WT30-SMD16
WT30-SMD16-1

24 VDC

 

E95399

WE70-AP
WE70-CL

E312669

 

The WT30 have a DC power supply. Be sure the following conditions are met.
Connect to one of the following circuits ((1) or (2)).

 

(1) Limited-voltage/current circuit conforming to UL508
A circuit that uses, as the power supply, the secondary wiring of an insulating transformer
Maximum voltage (no-load state): 30 Vrms (42.4 V peak) max.
Maximum current:

1) 8 A max. (including short-circuited state) or

2) The current is limited with a circuit-protection device (e.g., fuse) of the ratings shown in the following table:

 

No-load voltage (V peak)

Maximum current rating (A)

0 to 20

5.0

Greater than 20 V peak,

no greater than 30 V peak

100/Peak voltage

 

(2) A Class 2 power supply unit conforming to UL1310 or circuit with maximum voltage of 30 Vrms (42.4 V peak) that uses, as the power supply, a Class 2 transformer to conforming UL1585.

 

Note: Group C: Combustible gas/vapor, example: ethylene

 

 

Code Readers

 

Model

File No.

Ratings

V530-R150V3

E104818

See below.

 

The above models have a DC power supply. Be sure the following conditions are met.
Connect to one of the following circuits ((1) or (2)).

 

(1) Limited-voltage/current circuit conforming to UL508
A circuit that uses, as the power supply, the secondary wiring of an insulating transformer
Maximum voltage (no-load state): 30 Vrms (42.4 V peak) max.
Maximum current:

1) 8 A max. (including short-circuited state) or

2) The current is limited with a circuit-protection device (e.g., fuse) of the ratings shown in the following table:

 

No-load voltage (V peak)

Maximum current rating (A)

0 to 20

5.0

Greater than 20 V peak,

no greater than 30 V peak

100/Peak voltage value

 

(2) A Class 2 power supply unit conforming to UL1310 or circuit with maximum voltage of 30 Vrms (42.4 V peak) that uses, as the power supply, a Class 2 transformer to conforming UL1585

 

Note: Listing approvals

 

 

RFID Systems

 

Model

Standard No.

File No.

Marking

Listed/

Recognized

Category

Ratings/Remarks

CJ1W-V600C11
CJ1W-V600C12
CS1W-V600C11
CS1W-V600C12

UL508

E104818

cULus

Listed

NMTR/

NMTR7

 

CJ1W-V680C11
CJ1W-V680C12

UL508

E95399

cULus

Listed

NRAQ/

NRAQ7

 

CS1W-V680C11
CS1W-V680C12

V600-CA5D01

V600-CA5D02

Input: 24V DCV, 0.8A

V680-CA5D01-V2

V680-CA5D02-V2

UL508

E95399

cULus

Listed

NRAQ/

NRAQ7

Input: 24V DC, 0.8A

V680-HAM42-DRT

Input: 24V DC, 0.2A

V680-HAM42-FRT

Input: 24V DC, 0.3A

V680-HAM91

V680-HAM81

Input: 24V DCV, 0.15A

V750-BA50C04-US

UL60950-1

E256842

cULus

Listed

NWGQ/

NWGQ7

Input: 12V DC, 2.3A
A special AC Adapter is used.

 

The above models have a DC power supply. Be sure the following conditions are met.
Connect to one of the following circuits ((1) or (2)).

 

(1) Limited-voltage/current circuit conforming to UL508
A circuit that uses, as the power supply, the secondary wiring of an insulating transformer
Maximum voltage (no-load state): 30 Vrms (42.4 V peak) max.
Maximum current:

1) 8 A max. (including short-circuited state) or

2) The current is limited with a circuit-protection device (e.g., fuse) of the ratings shown in the following table:

 

No-load voltage (V peak)

Maximum current rating (A)

0 to 20

5.0

Greater than 20 V peak,

no greater than 30 V peak

100/Peak voltage value

 

(2) A Class 2 power supply unit conforming to UL1310 or circuit with maximum voltage of 30 Vrms (42.4 V peak) that uses, as the power supply, a Class 2 transformer to conforming UL1585

 