Safety Relay Unit (Sensor Connector Type)
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: July 11, 2019
Model | G9SA-300-SC |
---|---|
Power supply voltage | 24 VDC |
Operating voltage range | 85% to 110% of rated power supply voltage |
Power consumption | 24 VDC: 0.7 W max. |
Model
Load |
G9SA-300-SC |
---|---|
Resistive load | |
Rated load | 250 VAC, 5 A
30 VDC, 5 A |
Rated carry current | 5 A |
Model | G9SA-300-SC |
---|---|
Input current | 40 mA max. |
Model | G9SA-300-SC | ||
---|---|---|---|
Contact resistance *1 | 100 mΩ | ||
Operating time *2 | 300 ms max. | ||
Response time *3 | 10 ms max. | ||
Isolation
specification |
Isolation voltage (Ui) | 250 VAC | |
Impulse withstand voltage (Uimp) | 4 kV | ||
Insulation
resistance *4 |
Between input and output | 100 MΩ min. (at 500 VDC) | |
Between different poles
of output |
|||
Dielectric
strength |
Between input and output | 2,500 VAC 1min. | |
Between different poles
of output |
|||
Vibration resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm
double amplitude) |
||
Shock
resistance |
Destruction | 300 m/s2 | |
Malfunction | 100 m/s2 | ||
Durability | Mechanical | 5,000,000 operations min. (at approx. 7,200 operations/h) | |
Electrical | 100,000 operations min. (at approx. 1,800 operations/h, rated
load) |
||
Failure rate (P level) (reference value) | 5 VDC, 1 mA | ||
Ambient operating temperature | -25 to 55°C (with no icing or condensation) | ||
Ambient operating humidity | 35% to 85% | ||
Terminal tightening torque | 0.98 N·m | ||
Weight | Approx. 300 g |
last update: July 11, 2019