Solid-state Timer
last update: February 1, 2024
| Item | H3DS-ML[] | H3DS-SL[] | H3DS-AL[] |
|---|---|---|---|
| Operating mode | A: ON-delay (Signal or Power)
B: Flicker OFF start (Signal or Power) B2: Flicker ON start (Signal or Power) C: Signal ON/OFF-delay D: Signal OFF-delay E: Interval (Signal or Power) G: Signal ON/OFF-delay J: One-shot (Signal or Power) |
A: ON-delay
B2: Flicker ON start E: Interval J: One-shot |
A: ON-delay (fixed) |
| Input type | Voltage input | --- | |
| Output type | Relay: SPDT | ||
| External connections | Screw terminal, Screw-Less Clamp | ||
| Terminal block | Screw terminal type: Clamps two 2.5-mm2 max. bar terminals without sleeves.
Screw-Less Clamp type: Clamps two 1.5-mm2 max. bar terminals without sleeves. |
||
| Terminal screw
tightening torque |
0.98 Nm max. | ||
| Mounting method | DIN track mounting * | ||
| Attachment | Nameplate label | ||
| Approved standards | UL508, CSA C22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100 |
||
* Can be mounted to 35-mm DIN Track with a plate thickness of 1 to 2.5 mm.
| Time scale display | Time range |
|---|---|
| 0.1 s | 0.1 to 1.2 s |
| 1 s | 1 to 12 s |
| 0.1 m | 0.1 to 1.2 min |
| 1 m | 1 to 12 min |
| 0.1 h | 0.1 to 1.2 h |
| 1 h | 1 to 12 h |
| 10 h | 10 to 120 h |
Note: When the time setting dial is set to "0" for any time scale, the output will operate instantaneously.
| Rated supply voltage *1, *2 | 24 to 230 VAC (50/60 Hz)/24 to 48 VDC |
|---|---|
| Operating voltage range | 85% to 110% of rated supply voltage |
| Power reset | Minimum power-off time: 0.1 s |
| Reset voltage | 2.4 VAC/DC max. |
| Power consumption *3 | AC:
32 VA max./3.0 W max. (typical: 30 VA/2.7 W) at 230 VAC DC: 0.7 W max. (typical: 0.6 W) at 24 VDC 1.4 W max. (typical: 1.3 W) at 48 VDC |
| Voltage input | Max. permissible capacitance between inputs lines (terminals B1 and A2): 2,000 pF
Load connectable in parallel with inputs (terminals B1 and A1). H-level: 20.4 to 253 VAC/20.4 to 52.8 VDC L-level: 0 to 2.4 VAC/DC |
| Control output | Contact output:
5 A at 250 VAC with resistive load (cosφ = 1) 1 A at 250 VAC with inductive load (cosφ = 0.3) 5 A at 30 VDC with resistive load (cosφ = 1) 0.15 A max. at 125 VDC with resistive load, 0.1 A max. at 125 VDC with L/R of 7 ms. The minimum applicable load is 10 mA at 5 VDC (P reference value). Contact materials: Ag-alloy |
| Ambient temperature | Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing) |
| Ambient humidity | Operating: 35% to 85% |
| Accuracy of operating
time |
±1% max. of FS (±1% ±10 ms max. at 1.2-s range) |
|---|---|
| Setting error | ±10% ±50 ms max. of FS |
| Signal input time | 50 ms min. |
| Influence of voltage | ±0.7% max. of FS (±0.7% ±10 ms max. at 1.2-s range) |
| Influence of
temperature |
±5% max. of FS (±5%±10 ms max. at 1.2-s range) |
| Insulation resistance | 100 MΩ min. at 500 VDC |
| Dielectric strength | Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000
VAC for 1 min. Between control output terminals and operating circuit: 2,000 VAC for 1 min. Between contacts not located next to each other: 1,000 VAC for 1 min. |
| Vibration resistance | Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz |
| Shock resistance | Malfunction: 100 m/s2 3 times each in 6 directions
Destruction: 1,000 m/s2 3 times each in 6 directions |
| Impulse withstand
voltage |
5 kV (between power terminals)
5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts) |
| Noise immunity | Square-wave noise generated by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
±1.5 kV |
| Static immunity | Malfunction: 4 kV
Destruction: 8 kV |
| Life expectancy | Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) * |
| EMC | (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class B Emission AC Mains: EN55011 Group 1 class B Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering: EN61000-3-3 (EMS) EN61812-1 Immunity ESD: IEC61000-4-2 Immunity RF-interference: IEC61000-4-3 Immunity Burst: IEC61000-4-4 Immunity Surge: IEC61000-4-5 Immunity Conducted Disturbance: IEC61000-4-6 Immunity Voltage Dip/Interruption: IEC61000-4-11 |
| Case color | Light gray (5Y7/1) |
| Degree of protection | IP30 (Terminal block: IP20) |
| Weight | Approx. 70 g |
| Item | H3DS-F |
|---|---|
| Operating mode | Flicker-OFF/Flicker-ON start |
| Output type | Relay: SPDT |
| External connections | Screw terminal, Screw-Less Clamp |
| Terminal block | Screw terminal type: Clamps two 2.5-mm2 max. bar terminals without sleeves.
Screw-Less Clamp type: Clamps two 1.5-mm2 max. bar terminals without sleeves. |
| Terminal screw
tightening torque |
0.98 Nm max. |
| Mounting method | DIN track mounting * |
| Attachment | Nameplate label |
| Approved standards | UL508, CSA C22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P 100 |
* Can be mounted to 35-mm DIN Track with a plate thickness of 1 to 2.5 mm.
| Time scale display | Time range |
|---|---|
| 0.1 s | 0.1 to 1.2 s |
| 1 s | 1 to 12 s |
| 0.1 m | 0.1 to 1.2 min |
| 1 m | 1 to 12 min |
| 0.1 h | 0.1 to 1.2 h |
| 1 h | 1 to 12 h |
Note: When the time setting dial is set to “0” for any time scale, the output will operate instantaneously.
| Rated supply voltage * | 24 to 230 VAC (50/60 Hz)/24 to 48 VDC |
|---|---|
| Operating voltage range | 85% to 110% of rated supply voltage |
| Power reset | Minimum power-off time: 0.1 s |
| Reset voltage | 2.4 VAC/DC max. |
| Power consumption | AC:
33 VA max./2.2 W max. (typical: 31 VA/2.0 W) at 230 VAC DC: 0.7 W max. (typical: 0.6 W) at 24 VDC 1.4 W max. (typical: 1.2 W) at 48 VDC |
| Voltage input | Max. permissible capacitance between inputs lines (terminals B1 and A2): 2,000 pF
Load connectable in parallel with inputs (terminals B1 and A1). H-level: 20.4 to 253 VAC/20.4 to 52.8 VDC L-level: 0 to 2.4 VAC/DC |
| Control output | Contact output:
5 A at 250 VAC with resistive load (cosφ = 1) 1 A at 250 VAC with inductive load (cosφ = 0.3) 5 A at 30 VDC with resistive load (cosφ = 1) |
| Ambient temperature | Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing) |
| Ambient humidity | Operating: 35% to 85% |
* DC ripple rate: 20% max.
| Accuracy of operating
time |
±1% max. of FS (±1% ±10 ms max. at 1.2-s range) |
|---|---|
| Setting error | ±10% ± 50 ms max. of FS |
| Influence of voltage | ±0.5% max. of FS (±0.5% ±10 ms max. at 1.2-s range) |
| Influence of
temperature |
±5% max. of FS (±5% ± 10 ms max. at 1.2-s range) |
| Insulation resistance | 100 MΩ min. at 500 VDC |
| Dielectric strength | Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000
VAC (50/60 Hz) for 1 min. Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min. Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min. |
| Impulse withstand
voltage |
3 kV (between power supply terminals)
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts) |
| Noise immunity | Square-wave noise generated by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
±1.5 kV |
| Static immunity | Malfunction: 4 kV
Destruction: 8 kV |
| Vibration resistance | Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz |
| Shock resistance | Malfunction: 200 m/s2, 3 times each in 6 directions
Destruction: 300 m/s2, 3 times each in 6 directions |
| Life expectancy | Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) * |
| EMC | (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class B Emission AC Mains: EN55011 Group 1 class B Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering: EN61000-3-3 (EMS) EN61812-1 Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3), 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3), 1 kV control port with capacitive clamp (level 3) Immunity Surge: EN61000-4-5: 2 kV common mode (level 3), 1 kV differential mode (level 3) |
| Case color | Light gray (5Y7/1) |
| Degree of protection | IP30 (IP20 for terminal block) |
| Weight | Approx. 70 g |
| Item | H3DS-G |
|---|---|
| Operating mode | Star-delta operation |
| Operating/Reset method | Time-limit operation/Self-reset |
| External connections | Screw terminal, Screw-Less Clamp |
| Terminal block | Screw terminal type: Clamps two 2.5-mm2 max. bar terminals without sleeves.
Screw-Less Clamp type: Clamps two 1.5-mm2 max. bar terminals without sleeves. |
| Terminal screw tightening
torque |
0.98 Nm max. |
| Output type | (Star operation circuit) Relay: SPST-NO
(Delta operation circuit) Relay: SPST-NO |
| Mounting method | DIN track mounting (see note) |
| Attachment | Nameplate label |
| Approved standards | UL508, CSA C22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100 |
* Can be mounted to 35-mm DIN Track with a plate thickness of 1 to 2.5 mm.
| Time scale | Star operation time ranges | |
|---|---|---|
| x 1 | 1 to 12 s | |
| x 10 | 10 to 120 s | |
| Star-delta transfer time | Programmable at 0.05 s, 0.1 s, 0.5 s, or 1 s |
|---|
| Rated supply voltage * | 24 to 230 VAC (50/60 Hz)/24 to 48 VDC |
|---|---|
| Operating voltage range | 85% to 110% of rated supply voltage |
| Power reset | Minimum power-off time: 0.5 s |
| Reset voltage | 2.4 VAC/DC max. |
| Power consumption | AC:
21 VA max./1.7 W max. (typical: 20 VA/1.6 W) at 230 VAC DC: 1.3 W max. (typical: 1.2 W) at 24 VDC 0.7 W max. (typical: 0.6 W) at 48 VDC |
| Control output | Contact output:
5 A at 250 VAC with resistive load (cosφ = 1) 1 A at 250 VAC with inductive load (cosφ = 0.3) 5 A at 30 VDC with resistive load (cosφ = 1) |
| Ambient temperature | Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing) |
| Ambient humidity | Operating: 35% to 85% |
* DC ripple rate: 20% max.
| Accuracy of operating
time |
±1% max. of FS |
|---|---|
| Setting error | ±10% ± 50 ms max. of FS |
| Total tolerance of
transfer time |
± (25% FS + 5 ms) max. |
| Influence of voltage | ±0.5% max. of FS |
| Influence of
temperature |
±5% max. of FS |
| Insulation resistance | 100 MΩ min. at 500 VDC |
| Dielectric strength | Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000
VAC (50/60 Hz) for 1 min. Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min. Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min. |
| Impulse withstand
voltage |
3 kV (between power supply terminals)
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts) |
| Noise immunity | Square-wave noise generated by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
±1.5 kV |
| Static immunity | Malfunction: 4 kV
Destruction: 8 kV |
| Vibration resistance | Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz |
| Shock resistance | Malfunction: 200 m/s2, 3 times each in 6 directions
Destruction: 300 m/s2, 3 times each in 6 directions |
| Life expectancy | Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) * |
| EMC | (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class B Emission AC Mains: EN55011 Group 1 class B Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering: EN61000-3-3 (EMS) EN61812-1 Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3), 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3), 1 kV control port with capacitive clamp (level 3) Immunity Surge: EN61000-4-5: 2 kV common mode (level 3), 1 kV differential mode (level 3) |
| Case color | Light gray (5Y7/1) |
| Degree of protection | IP30 (IP20 for terminal block) |
| Weight | Approx. 70 g |
| Item | H3DS-X |
|---|---|
| Operating mode | ON-delay |
| Operating/Reset method | Time-limit operation/self-resetting |
| Output type | SCR output |
| External connections | Screw terminal, Screw-Less Clamp |
| Terminal block | Screw terminal type: Clamps two 2.5-mm2 max. bar terminals without sleeves.
Screw-Less Clamp type: Clamps two 1.5-mm2 max. bar terminals without sleeves. |
| Terminal screw tightening
torque |
0.98 Nm max. |
| Mounting method | DIN track mounting * |
| Attachment | Nameplate label |
| Approved standards | UL508, CSA C22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100 |
* Can be mounted to 35-mm DIN Track with a plate thickness of 1 to 2.5 mm.
| Time scale display | Time range |
|---|---|
| 0.1 s | 0.1 to 1.2 s |
| 1 s | 1 to 12 s |
| 0.1 m | 0.1 to 1.2 min |
| 1 m | 1 to 12 min |
| 0.1 h | 0.1 to 1.2 h |
| 1 h | 1 to 12 h |
| 10 h | 10 to 120 h |
Note: When the time setting dial is set to “0” for any time scale, the output will operate instantaneously.
| Rated supply voltage * | 24 to 230 VAC/VDC (50/60 Hz) |
|---|---|
| Operating voltage range | 85% to 110% of rated supply voltage |
| Power reset | Minimum power-off time: 0.1 s |
| Reset voltage | 1.0 VAC/VDC max. |
| Reset current | 5 mA max. |
| Power consumption | 5 mA max. |
| Control output | SCR output: 5 mA to 0.7 A |
| Ambient temperature | Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing) |
| Ambient humidity | Operating: 35% to 85% |
* The ripple in DC power supply must be 5% max.
| Accuracy of operating
time |
±1% max. of FS (±1% ±10 ms max. at 1.2-s range) |
|---|---|
| Setting error | ±10% ± 50 ms max. of FS |
| Reset time | 0.1 s max. |
| Influence of voltage | ±0.5% max. of FS (±0.5%±10 ms max. at 1.2-s range) |
| Influence of
temperature |
±5% max. of FS (±5%±10 ms max. at 1.2-s range) |
| Insulation resistance | 100 MΩ min. at 500 VDC |
| Dielectric strength | Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000
VAC for 1 min |
| Impulse withstand
voltage |
3 kV (between power supply terminals)
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts) |
| Noise immunity | Square-wave noise generated by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
±1.5 kV (between power supply terminals) |
| Static immunity | Malfunction: 4 kV
Destruction: 8 kV |
| Vibration resistance | Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz |
| Shock resistance | Malfunction: 200 m/s2, 3 times each in 6 directions
Destruction: 300 m/s2, 3 times each in 6 directions |
| EMC | (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class B Emission AC Mains: EN55011 Group 1 class B Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering: EN61000-3-3 (EMS) EN61812-1 Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3), 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3), 1 kV control port with capacitive clamp (level 3) Immunity Surge: EN61000-4-5: 2 kV common mode (level 3), 1 kV differential mode (level 3) |
| Case color | Light gray (5Y7/1) |
| Degree of protection | IP30 (IP20 for terminal block) |
| Weight | Approx. 70 g |
last update: February 1, 2024