* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: October 19, 2020
Model | KE1-
PGR1C- FLK (Power/ Earth Leakage) |
KE1-
PVS1C- FLK (Power/ Momentary Voltage Sag) |
KE1-
VSU1B- FLK (Momentary Voltage Sag) |
KE1-
VAU1B- FLK (Voltage/ Current) |
KE1-
CTD8E (CT Expansion) |
KE1-
ZCT8E (ZCT Expansion) |
|
---|---|---|---|---|---|---|---|
Applicable phase wiring
method |
Single-phase two-wire, single-phase three-wire, three-phase three-wire, and three-
phase four-wire |
||||||
Power
supply |
Rated power
supply voltage |
100 to 240 VAC, 50/60 Hz | --- | ||||
Allowable supply
voltage range |
85% to 110% of rated power supply voltage | --- | |||||
Power supply
fluctuation frequency range |
45 to 65 Hz | --- | |||||
Power
consumption |
Standalone: 10 VA max.,
Maximum connections: 14 VA max. |
10 VA max. | |||||
Power
interruption compensation method |
--- | Backup for 1.2 seconds min.
with electric double-layer capacitor for voltage measurement only. |
--- | ||||
Input | Rated input
voltage |
100 to 480 VAC (single-phase, 2-wire): Line voltage
100/200 VAC (single-phase, 3-wire): Phase voltage/line voltage 100 to 480 VAC (3-phase, 3-wire): Line voltage 58 to 277 VAC/100 to 480 VAC (3-phase, 4-wire): Phase voltage/line voltage |
--- | ||||
Rated input
current for CT |
5 A, 50 A, 100 A, 200 A,
400 A, or 600 A Special CTs used. |
--- | 5 A, 50 A, 100 A, 200 A,
400 A, or 600 A Special CTs used. |
--- | |||
Rated input
current for ZCT |
50 A, 100 A,
150 A, 200 A, 400 A, 600 A, or 1,000 A |
--- | 50 A, 100 A,
150 A, 200 A, 400 A, 600 A, or 1,000 A |
||||
Rated input
power |
With 5-A CT: 4 kW
With 50-A CT: 40 kW With 100-A CT: 80 kW With 200-A CT: 160 kW With 400-A CT: 320 kW With 600-A CT: 480 kW |
--- | With 5-A CT:
4 kW With 50-A CT: 40 kW With 100-A CT: 80 kW With 200-A CT: 160 kW With 400-A CT: 320 kW With 600-A CT: 80 kW |
--- | |||
Rated input
frequency |
50/60 Hz | --- | |||||
Input frequency
fluctuation range |
45 to 65 Hz | --- | |||||
Input leakage
current |
1,000 mA | --- | 1,000 mA | ||||
Allowable input
voltage |
110% of rated input voltage (continuous) | --- | |||||
Allowable input
current |
120% of rated input current
(continuous) |
--- | 120% of rated current
(continuous) |
--- | |||
Rated input load | Voltage input: 0.5 VA max. (excluding power supply) | --- | |||||
Current input: 0.5 VA max. (for each input) | --- | Current
input: 0.5 VA max. (for each input) |
--- | ||||
Clock | Clock setting | 2012 to 2099 (Adjusted for leap years during this period.) | --- | ||||
Clock accuracy | ±1.5 min./month (at 23°C) | --- | |||||
Clock backup
period |
Seven-day backup with an electric double-layer
capacitor (after being powered for at least 24 hours and when the power is interrupted at 23°C) |
--- | |||||
Ambient operating
temperature |
-10 to 55°C (with no condensation or icing) | ||||||
Storage temperature | -25 to 65°C (with no condensation or icing) | ||||||
Ambient operating humidity | 25% to 85% | ||||||
Storage humidity | 25% to 85% | ||||||
Altitude | 2,000 m max. | ||||||
Installation environment | Overvoltage category II, pollution degree 2, measurement category II | ||||||
Compliant
standards |
All KE1 Units | EN 61010-2-030 (IEC 61010-2-030)
EN61326-1 Industrial electromagnetic environment UL61010-1 UL61010-2-030 |
Model | KE1-
PGR1C- FLK (Power/ Earth Leakage) |
KE1-
PVS1C- FLK (Power/ Momentary Voltage Sag) |
KE1-
VSU1B- FLK (Momentary Voltage Sag) |
KE1-
VAU1B- FLK (Voltage/ Current) |
KE1-
CTD8E (CT Expansion) |
KE1-
ZCT8E (ZCT Expansion) |
|
---|---|---|---|---|---|---|---|
Accuracy
*1 |
Voltage | ±1.0% FS ±1 digit
The accuracy of the voltage across the Vtr is ±2.0% FS ±1 digit under the same conditions. |
--- | ||||
Current | ±1.0% FS ±1 digit
However, the accuracy is ±2.0% FS ±1 digit for the phase-S current for a three-phase, three-wire circuit and the phase-N current for a single-phase, three-wire circuit under the same conditions. |
--- | ±1.0% FS ±1 digit
However, the accuracy is ±2.0% FS ±1 digit for the phase-S current for a three-phase, three- wire circuit and the phase-N current for a single-phase, three-wire circuit under the same conditions. |
--- | |||
Leakage current | 30 to 200
mA: ±5% rdg ±1 digit 200 to 1,000 mA: ±1%FS ±1 digit |
--- | 30 to 200
mA: ±5% rdg ±1 digit 200 to 1,000 mA: ±1%FS ±1 digit |
||||
Power (active
power and reactive power) |
Active power and reactive
power ±2.0% FS ±1 digit (power factor = 1) |
--- | Active
power and reactive power ±2.0% FS ±1 digit (Power factor = 1) |
--- | |||
Frequency | ±0.3 Hz ±1 digit | --- | |||||
Power factor *2 | ±5.0% FS (power factor =
0.5 to 1 to 0.5) |
--- | ±5.0% FS
(Power factor = 0.5 to 1 to 0.5) |
--- | |||
Temperature | --- | ||||||
Temperature influence *1 | ±1.0% FS (percentage of the measurement value at an ambient temperature of 23°C,
rated input, rated frequency, and a power factor of 1 in the operating temperature range) |
||||||
Frequency influence *1 | ±1.0% FS (percentage of the measurement value at an ambient temperature of 23°C,
rated input, rated frequency, and a power factor of 1 in the rated frequency ±5 Hz range) |
||||||
Influence of harmonics *1 | ±0.5% FS (at ambient temperature of 23°C, error for superimposed 2nd, 3rd, 5th,
7th, 9th, 11th, and 13th harmonics for a content percentage of 30% for current and 5% for voltage of the basic wave) |
||||||
Low-cut current set value | 0.1% to 19.9% of rated input
in 0.1% increments |
--- | 0.1% to 19.9% of rated
input in 0.1% increments |
--- | |||
Low-cut leakage current
set value |
Variable in 0.1-mA
increments between 0.1 and 30.0 mA |
--- | Variable in
0.1-mA increments between 0.1 and 30.0 mA |
||||
Sampling cycle | 100 ms for measurement voltage at 50 Hz and 83.3 ms for measurement voltage at
60 Hz |
||||||
Insulation resistance | Insulation resistance: 20 MΩ (at 500 VDC) | ||||||
Dielectric strength | All models: Locations to which 2,000 V was applied for one minute: Between all
terminals and case KE1-PGR1C-FLK: Between the power supply terminals and RS-485/transistor/relay outputs Between the power supply terminals and current/voltage/earth leakage inputs Between current/voltage/earth leakage inputs and RS-485/relay/transistor outputs KE1-PVS1C-FLK: Between the power supply terminals and RS-485/transistor/relay outputs Between the power supply terminals and current/voltage input Between current/voltage inputs and RS-485/relay/transistor outputs KE1-VSU1B-FLK: Between power supply terminals and RS-485/relay outputs Between the power supply terminals and voltage inputs Between voltage inputs and RS-485/relay outputs KE1-VAU1B-FLK: Between power supply terminals and RS-485/relay outputs Between the power supply terminals and current/voltage input Between current/voltage inputs and RS-485/relay outputs KE1-CTD8E: Between current inputs and relay outputs KE1-ZCT8E: Between earth leakage inputs and relay outputs |
||||||
Vibration resistance | Single-amplitude: 0.35 mm, Acceleration: 50 m/s2
Vibration: 10 to 55 Hz, 10 sweeps of 5 minutes each along 3 axes |
||||||
Shock resistance | 150 m/s2, 3 times each in 6 directions (up/down, left/right, forward/backward) | ||||||
Weight | Approx. 230 g | ||||||
Memory backup | No. of writes to non-volatile memory: 1,000,000 times | ||||||
Event
inputs |
Number of inputs | --- | |||||
No-voltage
inputs |
--- | ||||||
Voltage input | --- | ||||||
Tempera-
ture in- puts |
Thermistor
inputs |
--- | |||||
Applicable
thermistor |
--- | ||||||
Combinations | Capable of supporting 7
event inputs and 1 temperature input when connected with the KM1-EMU8A-FLK. |
--- | |||||
Transis-
tor out- puts |
Number of
outputs |
One open-collector output
(OUT2) |
--- | ||||
Output capacity | 30 VDC, 30 mA | --- | |||||
ON residual
voltage |
1.2 V max. | --- | |||||
OFF leakage
current |
100 μA max. | --- | |||||
Total power
consumption pulse output |
Outputs one pulse when
the power consumption reaches the set pulse output unit (1, 10, 100, 1k, 2k, 5k, 10k, 20k, 50k, 100k W/h). |
--- | |||||
Alarm output | Outputs an alarm based on
the set alarm output threshold. |
--- | |||||
Alarm recovery
method |
Automatic recovery only | --- | |||||
Relay
outputs |
Number of
outputs |
One NO
contact output (OUT1) |
--- | One NO
contact output (OUT1) |
Two NO
contact outputs (OUT1 and OUT2) |
One NO contact output
(OUT1) |
|
Rated load | Resistance
load, 250 VAC, 3 A; 30 VDC, 3 A Inductive load (cosφ = 0.4, L/R = 7 ms): 250 VAC, 1 A; 30 VDC, 1 A |
--- | Resistance load, 250 VAC,
3 A; 30 VDC, 3 A Inductive load (cosφ = 0.4, L/R = 7 ms): 250 VAC, 1 A; 30 VDC, 1 A |
Resistance load, 125 VAC,
3 A; 30 VDC, 3 A |
|||
Mechanical life
expectancy |
10,000,000
operations |
--- | 10,000,000 operations | 5,000,000 operations min. | |||
Electrical life
expectancy |
50,000
operations min. (rated load switching frequency: 1,800 times/h) |
--- | 50,000 operations min.
(rated load switching frequency: 1,800 times/h) |
200,000 times min. (rated
load switching frequency: 1,800 times/h) |
|||
Failure rate P
level |
5 VDC, 10
mA (at a switching frequency of 120 times/min) |
--- | 5 VDC, 10 mA (at a switching frequency of 120 times/
min) |
||||
Alarm output | Turns
output ON or OFF based on the alarm set value. |
--- | Turns output ON or OFF based on the alarm set value. | ||||
Recovery
method |
Automatic
recovery only |
--- | Automatic recovery only | ||||
Semicon
ductor relay outputs |
Number of
outputs |
--- | One MOS
FET output (OUT1) |
One MOS
FET output (OUT2) |
--- | ||
Maximum load
voltage |
--- | Peak: 24 VAC/DC | --- | ||||
Continuous load
current |
--- | Peak: 80 mA AC/DC | --- | ||||
ON resistance | --- | 15 Ω max. | --- | ||||
Open-circuit
leakage current |
--- | 1 nA max. | --- | ||||
Alarm output | --- | Turns output ON or OFF
based on the alarm set value. |
--- | ||||
Recovery
method |
--- | Automatic recovery only | --- | ||||
Commu-
nications |
Protocols | Communications protocol setting OFF: CompoWay/F, ON: Modbus | |||||
Unit number
setting |
CompoWay/F: 0 to 99, Modbus:1 to 99
When a switch operation is performed to set the protocol to Modbus when the node number is set to 0, the node number is automatically changed to 1. |
||||||
Communication
items |
Refer to the KM1/KE1 Communications Manual. | ||||||
RS-485 | Sync method | Start-stop | --- | ||||
Baud rate | 9,600 bps, 19,200 bps, or 38,400 bps | --- | |||||
Transmission
code |
CompoWay/F: ASCII, Modbus: Binary | --- | |||||
Data length | CompoWay/F: 7 bits, 8 bits; Modbus: 8 bits | --- | |||||
Stop bits | CompoWay/F: 1 bits or 2 bits
Modbus: 1 bit with priority, 2 bits without priority |
--- | |||||
Parity | Even, odd, or none | --- | |||||
Maximum
transmission distance |
500 m | --- | |||||
Maximum number
of nodes |
CompoWay/F: 31, Modbus: 99 | --- | |||||
USB | USB 1.1 compliant | ||||||
Memory retention for power
interruptions |
Parameter
data, alarm history, logged data, and backup data |
Parameter
data, alarm history, logged data, backup data, and momentary voltage sag history |
Parameter
data, alarm history, logged data, and momentary voltage sag history |
Parameter
data, alarm history, and logged data |
Parameter
data, alarm history, and backup data |
Parameter
data and alarm history |
|
Number of connect
connector insertions/ removals |
25 times |
Model | KE1-
PGR1C- FLK (Power/ Earth Leakage) |
KE1-
PVS1C- FLK (Power/ Momentary Voltage Sag) |
KE1-
VSU1B- FLK (Momentary Voltage Sag) |
KE1-
VAU1B- FLK (Voltage/ Current) |
KE1-
CTD8E (CT Expansion) |
KE1-
ZCT8E (ZCT Expansion) |
|
---|---|---|---|---|---|---|---|
Voltage
monitor- ing |
Alarm threshold
(overvoltage/ undervoltage) |
0.0 to 12,100.0 V | --- | ||||
Operation
characteristic |
±1.0% FS ±1 digit
The accuracy of the voltage across the Vtr is ±2.0% FS ±1 digit under the same conditions. |
--- | |||||
Alarm ON delay
(overvoltage/ undervoltage) |
0.1 to 10.0 s | --- | |||||
Operating time
characteristic |
±0.2 s | --- | |||||
Alarm hysteresis
(overvoltage/ undervoltage) |
0.0 to 2,200.0 V | --- | |||||
Resetting time | 0.5 s (Cannot be changed.) | --- | |||||
Resetting time
characteristic |
±0.2 s | --- | |||||
Current
monitor- ing |
Alarm threshold
(overcurrent/ undercurrent) |
0.0 to 6,000.0 A | --- | 0.0 to 6,000.0 A | --- | ||
Operation
characteristic |
±1.0% FS ±1 digit
However, the accuracy is ±2.0% FS ±1 digit for the phase-S current for a three-phase, three-wire circuit and the phase-N current for a single- phase, three-wire circuit under the same conditions. |
--- | ±1.0% FS ±1 digit
However, the accuracy is ±2.0% FS ±1 digit for the phase-S current for a three-phase, three- wire circuit and the phase-N current for a single-phase, three- wire circuit under the same conditions. |
--- | |||
Alarm ON delay
(overcurrent/ undercurrent) |
0.1 to 10.0 s | --- | 0.1 to 10.0 s | --- | |||
Operation
characteristic |
±0.2 s | --- | ±0.2 s | --- | |||
Alarm hysteresis
(overcurrent/ undercurrent) |
0.0 to 1,000.0 A | --- | 0.0 to 1,000.0 A | --- | |||
Resetting time | 0.5 s (Cannot be changed.) | --- | 0.5 s (Cannot be
changed.) |
--- | |||
Resetting time
characteristic |
±0.2 s | --- | ±0.2 s | --- | |||
Active
power monitor- ing |
Alarm thresholds
(upper limit/lower limit) |
-120,000,000 to
120,000,000 W |
--- | -120,000,000
to 120,000,000 W |
--- | ||
Operation
characteristic |
±2.0% FS ±1 digit | --- | ±2.0% FS
±1 digit |
--- | |||
Alarm ON delay
(upper limit/lower limit) |
0.5 to 10.0 s | --- | 0.5 to 10.0 s | --- | |||
Operation
characteristic |
±0.2 s | --- | ±0.2 s | --- | |||
Alarm hysteresis
(upper limit/lower limit) |
0 to 24,000,000 W | --- | 0 to
24,000,000 W |
--- | |||
Resetting time | 0.5 s (Cannot be changed.) | --- | 0.5 s (Cannot
be changed.) |
--- | |||
Resetting time
characteristic |
±0.2 s | --- | ±0.2 s | --- | |||
Reactive
power monitor- ing |
Alarm thresholds
(upper limit/lower limit) |
-120,000,000 to
120,000,000 W |
--- | -120,000,000
to 120,000,000 W |
--- | ||
Operation
characteristic |
±2.0% FS ±1 digit | --- | ±2.0% FS
±1 digit |
--- | |||
Alarm ON delay
(upper limit/lower limit) |
0.5 to 10.0 s | --- | 0.5 to 10.0 s | --- | |||
Operation
characteristic |
±0.2 s | --- | ±0.2 s | --- | |||
Alarm hysteresis
(upper limit/lower limit) |
0 to 24,000,000 W | --- | 0 to
24,000,000 W |
--- | |||
Resetting time | 0.5 s (Cannot be changed.) | --- | 0.5 s (Cannot
be changed.) |
--- | |||
Resetting time
characteristic |
±0.2 s | --- | ±0.2 s | --- | |||
Power
factor monitor- ing |
Alarm threshold | -1.00 to 1.00 | --- | -1.00 to 1.00 | --- | ||
Operation
characteristic |
±5.0% FS (Power factor =
0.5 to 1 to 0.5) |
--- | ±5.0% FS
(Power factor = 0.5 to 1 to 0.5) |
--- | |||
Alarm ON delay | 0.5 to 10.0 s | --- | 0.5 to 10.0 s | --- | |||
Operation
characteristic |
±0.2 s | --- | ±0.2 s | --- | |||
Alarm hysteresis | 0.00 to 1.00 | --- | 0.00 to 1.00 | --- | |||
Earth
leakage monitor- ing |
Earth leakage
comparison value |
30 to
1,000 mA |
--- | 30 to 1,000 mA | |||
Operation
characteristic |
±5% rdg
±1 digit for 30 to 200 mA, ±1% FS ±1 digit for 200 to 1,000 mA |
--- | ±5% rdg ±1 digit for 30 to
200 mA, ±1% FS ±1 digit for 200 to 1,000 mA |
||||
Earth leakage
operating time |
0.1 to
20.0 s |
--- | 0.1 to 20.0 s | ||||
Operation
characteristic |
±0.2 s | --- | ±0.2 s | ||||
Resetting
condition |
95% of
operating value |
--- | 95% of operating value | ||||
Resetting time | 0.5 s
(Cannot be changed.) |
--- | 0.5 s (Cannot be changed.) | ||||
Momen-
tary volt- age sag monitor- ing |
Momentary voltage
sag detection voltage |
--- | 0 to 480.0 V | --- | |||
Allowable error in
detection voltage |
--- | ±2.5% FS ±1 digit | --- | ||||
Continuation time
for momentary voltage sag |
--- | Without backup: 0.02 to
0.2 s |
--- | ||||
With backup: 0.02 to 1.00 s | |||||||
Relay output
operating time accuracy |
--- | ±5 ms | --- | ||||
Open
phase monitor- ing |
Open phase
detection condition |
(Largest error between any phase voltage and
average voltage) ÷ Average voltage × 100 . 85% |
--- | ||||
Operation
characteristic |
±1.0% FS ±1 digit
The accuracy of the voltage across the Vtr is ±2.0% FS ±1 digit under the same conditions. |
--- | |||||
Operating time | 0.1 s | --- | |||||
Operation
characteristic |
±0.2 s | --- | |||||
Resetting
condition |
Non-balance ratio: Less than 13% | --- | |||||
Resetting time | 0.5 s (Cannot be changed.) | --- | |||||
Resetting time
characteristic |
±0.2 s | --- | |||||
Re-
versed phase monitor- ing |
Reversed phase
detection condition |
Change in voltage phase sequence lasts for 0.1
second or longer. |
--- | ||||
Operating time | 0.1 s | --- | |||||
Operation
characteristic |
±0.2 s | --- | |||||
Resetting
condition |
Phase offset within ±45° | --- | |||||
Resetting time | 0.5 s (Cannot be changed.) | --- | |||||
Resetting time
characteristic |
±0.2 s | --- |
Structure | Split-type | Through-
hole |
|||||
---|---|---|---|---|---|---|---|
Model | KM20-
CTF-5A |
KM20-
CTF-50A |
KM20-
CTF-100A |
KM20-
CTF-200A |
KM20-
CTF-400A |
KM20-
CTF-600A |
KM20-
CTB- 5A/50A |
Rated primary current | 5 A | 50 A | 100 A | 200 A | 400 A | 600 A | 5A/50 A |
Secondary winding | 3,000 turns | 6,000 turns | 9,000 turns | 3,000 turns | |||
Applicable frequency | 10 Hz to 5 kHz | ||||||
Insulation resistance | Between output terminals and case: 50 MΩ min. (at 500 VDC) | ||||||
Dielectric strength | Between output terminals and case: 2,000 VAC for 1 minute | ||||||
Protective element | 7.5-V clamp element | ||||||
Allowable number of
connections/ disconnections |
100 times | ||||||
Mountable wire
diameter |
7.4 mm
max. |
8.5 mm
max. |
11 mm max. | 24 mm max. | 35.5 mm max. | 8.4 mm
max. |
|
Operating
temperature and humidity ranges |
-20 to 60°C, 85% max. (with no condensation) | ||||||
Storage temperature
and humidity ranges |
-30 to 65°C, 85% max. (with no condensation) |
Note: Operate the Special CTs at a low voltage of 600 V or less.
Item | Specification |
---|---|
Rated power supply voltage | 100 to 240 VAC, 50/60 Hz |
Allowable voltage range | 85% to 110% of rated power supply voltage |
Power consumption (at maximum load) | 6 VA max. |
Current consumption (DeviceNet
power supply) |
45 mA max. (24 VDC) |
Vibration resistance | 10 to 55 Hz, 10 m/s2 for 2 hours along 3 axes |
Shock resistance | Single-amplitude: 0.35 mm, Acceleration: 50 m/s2 Vibration: 10 to 55 Hz,
10 sweeps of 5 minutes each along 3 axes |
Dielectric strength | 2,000 V for 1 min between all terminals and case, and between power
supply terminals and temperature input/RS-485 output/USB output/ DeviceNet output/transistor output |
Insulation resistance | 20 MΩ min. (at 500 VDC) |
Ambient operating temperature | -10 to 55°C (with no condensation or icing) |
Ambient operating humidity | 25% to 85% |
Ambient storage temperature | -25 to 65°C (with no condensation or icing) |
Dimensions | 45 × 90 × 110 mm (W×H×D) (excluding protrusions) |
Memory backup | EEPROM (non-volatile memory), No. of writes: 1,000,000 |
Weight | Approx. 170 g |
Model | KM20-CTF-CB3 |
---|---|
Cable length | 3 m |
Note: Use only the CT Cable specified by OMRON.
Structure | Indoor, through-hole | |||||
---|---|---|---|---|---|---|
Model | OTG-L21 | OTG-L30 | OTG-L42 | OTG-L68 | OTG-L82 | OTG-L156 |
Rated current | 50 A | 100 A | 200 A | 400 A | 600 A | 1,000 A |
Through-hole diameter | 21 | 30 | 42 | 68 | 82 | 156 |
Rated load | 600 VAC max, 50/60 Hz, Single-phase/three-phase | |||||
Output terminal
polarity |
Polarity (Connect CT output terminal k to terminal 5 or 7 and terminal I to terminal 6 or 8.) | |||||
Secondary connection | Terminals (with test terminals kt and lt) | |||||
Insulation resistance | 100 MΩ min. (between charged metal parts and ground) | |||||
Dielectric strength | 2,200 VAC at 50/60 Hz for 1min (between charged metal parts and ground) | |||||
Ambient operating
temperature |
-10 to 60°C (with no icing) | |||||
Ambient operating
humidity |
45% to 85% | |||||
Weight | Approx. 90 g | Approx. 130 g | Approx. 230 g | Approx. 480 g | Approx. 700 g | Approx. 6.6 kg |
Structure | Indoor, split-type | Outdoor,
through-hole |
Outdoor,
split-type |
||
---|---|---|---|---|---|
Model | OTG-CN52 | OTG-CN77 | OTGCN112 | OTG-LA30W | OTG-CN36W |
Rated current | 200 A | 400 A | 600 A | 100 A | 150 A |
Through-hole diameter | 52 | 77 | 112 | 30 | 36 |
Rated load | 600 VAC max, 50/60 Hz, Single-phase/three-phase | ||||
Output terminal polarity | Polarity (Connect CT output terminal k to terminal 5 or 7 and terminal I to terminal 6 or 8.) | ||||
Secondary connection | Terminals (with test terminals kt and lt) | Lead wire I = 500 | Lead wire I = 450 | ||
Insulation resistance | 100 MΩ min. (between charged metal parts and ground) | ||||
Dielectric strength | 2,200 VAC at 50/60 Hz for 1min (between charged metal parts and ground) | ||||
Ambient operating temperature | -10 to 60°C (with no icing) | ||||
Ambient operating humidity | 45% to 85% | ||||
Weight | Approx. 1.3 kg | Approx. 2.5 kg | Approx. 3.5 kg | Approx. 140 g | Approx. 650 g |
Note: Operate the Special ZCTs at a low voltage of 600 V or less.
last update: October 19, 2020