PROFIBUS-DP master unit
last update: February 6, 2014
Model | Remarks | ||
---|---|---|---|
CS1W-PRM21 | Main function | Basic PROFIBUS-DP master Class 1
functions plus: DPV1 data types support |
|
Unit No. | 0-15 | Special CPU unit | |
Maximum number of
units mountable per PLC |
16 | Maximum depends on PLC CPU-type | |
Configurator | FTD/DTM based | Incorporates a Generic DTM to use with GSD-file based slaves | |
Supported baud rate(s) | All baud rates as specified by the standard EN50170 Volume 2,
the PROFIBUS extensions to EN50170, as well as the standard IEC61158: 9.6 kBit/s, 19.2 kBit/s, 45.45 kBit/s. 93.75 kBit/s, 187.5 kBit/s, 500 kBit/s, 1.5 MBit/s, 3 MBit/s, 6 MBit/s, 12 MBit/s |
The baud rate value to be used
must be selected through the Configurator. |
|
Selectable
PROFIBUS address |
0-125 | Set through the configurator | |
Maximum number of
PROFIBUS slaves |
125 | ||
Maximum number of
I/O points |
7168 words | ||
Maximum number of
I/O points per PROFIBUS slave |
244 bytes In / 244 bytes Out | ||
Control and
status ares size |
25 words | ||
Supported
Global_Control services |
Sync
Unsync Freeze Unfreeze Clear |
Through Control Area | |
Supported
Master-Slave communication services |
Data_Exchange
Slave_Diag Set_PRM Chk_Cfg Global_Control |
||
Power consumption | 400 mA at 5 V | ||
Dimensions | 34.5 mm wide x 130 mm height x
111.2 mm depth |
||
Weight | 154 gr | ||
Ambient temperature | Operating: 0 °C to 50 °C |