NX-series EtherNet/IP™ Coupler Unit
last update: December 16, 2024
Item | Specification | |
---|---|---|
Enclosure | Mounted in a panel | |
Grounding method | Ground to 100 Ω or less | |
Operating
environment |
Ambient operating
temperature |
0 to 55°C |
Ambient operating
humidity |
10% to 95% (with no condensation or icing) | |
Atmosphere | Must be free from corrosive gases. | |
Ambient storage
temperature |
-25 to 70°C (with no condensation or icing) | |
Altitude | 2,000 m max. | |
Pollution degree | Pollution degree 2 or less: Meets IEC 61010-2-201. | |
Noise immunity | Conforms to IEC 61000-4-4. 2 kV (power supply line) | |
Overvoltage category | Category II: Meets IEC 61010-2-201. | |
EMC immunity level | Zone B | |
Vibration resistance | Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) *1 |
|
Shock resistance | Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions *1 | |
Applicable standards *2 | cULus: Listed UL508, ANSI/ISA 12.12.01
EU: EN 61131-2, C-Tick or RCM, KC: KC Registration |
Item | Specification | ||
---|---|---|---|
Model | NX-EIC202 | ||
Number of connectable
NX Units |
63 Units max.*1 | ||
Communications
protocols |
EtherNet/IP | ||
UDP/IP and TCP/IP (Message Services) | Number of buffers (sockets):
• 8 message buffers for server • No message buffers for client • Shared buffers for UDP/IP messages and TCP/IP messages Maximum message size: • Request: 492 bytes • Response: 496 bytes Maximum NX output data size: • 490 bytes Maximum NX input data size: • 496 bytes |
||
Modulation | Baseband | ||
Link speed | 100 Mbps | ||
Physical layer | 100BASE-TX (IEEE 802.3) | ||
Received Packet Interval
(RPI, refresh cycle) |
4 to 1,000 ms | ||
Allowed communications
bandwidth addressing to the local node |
1,000 pps | ||
Topology | Line, Tree, Star | ||
Ethernet Switch | Layer 2 Ethernet switch | ||
Transmission media | Category 5 or higher twisted-pair cable (Recommended cable:
double-shielded cable with aluminum tape and braiding) |
||
Transmission distance | Distance between nodes: 100 m or less | ||
NX bus I/O data size | Input: 512 bytes max. (including input data, status, and unused areas)
Output: 512 bytes max. (including output data and unused areas) |
||
EtherNet/IP I/O connection
size |
Input: 504 bytes max. (including input data, status, and unused areas)
Output: 504 bytes max. (including output data and unused areas) |
||
Refreshing methods | Free-Run refreshing | ||
Unit
power supply *2 |
Power supply voltage | 24 VDC (20.4 to 28.8 VDC) | |
NX Unit power supply
capacity |
10 W max. (Refer to Installation orientation and restrictions for details.) | ||
NX Unit power supply
efficiency |
70% | ||
Isolation method | No isolation between NX Unit power supply and Unit power supply terminals | ||
Current capacity of
power supply terminals |
4 A max. | ||
I/O
power supply *2 |
Power supply voltage | 5 to 24 VDC (4.5 to 28.8 VDC) *3 | |
Maximum I/O power
supply current |
10 A (Refer to Installation orientation and restrictions for details.) | ||
Current capacity of
power supply terminals |
10 A max. | ||
NX Unit power consumption | 1.60 W max. | ||
Current consumption from
I/O power supply |
10 mA max. (for 24 VDC) | ||
Dielectric strength | 510 VAC for 1 min, leakage current: 5 mA max. (between isolated circuits) | ||
Insulation resistance | 100 VDC, 20 MΩ min. (between isolated circuits) | ||
External connection
terminals |
Communications Connector
For EtherNet/IP communications. • RJ45 × 2 (shielded) |
||
Screwless Clamping Terminal Block
For Unit power supply, I/O power supply, and grounding. Removable. |
|||
Peripheral USB Port
For Sysmac Studio connection. • Physical layer: USB 2.0-compliant, B-type connector • Transmission distance: 5 m max. |
|||
Dimensions | 46 × 100 × 71 mm (W×H×D) | ||
Weight | 150 g max. | ||
Installation orientation
and restrictions |
Installation orientation: 6 possible orientations
Restrictions: • Used in the upright installation orientation. ![]() • Used in any other orientation than the upright installation orientation. ![]() |
||
Circuit layout | ![]() |
||
Terminal arrangement | ![]() |
||
Accessory | End Cover (NX-END01): 1 |
*1. Refer to the NX-series Safety Control Unit User's Manual (Cat. No. Z930) for the number of Safety Control Units that
can be connected.
*2. Refer to the NX-series EtherNet/IP™Coupler Unit User’s Manual (Cat. No. W536) for procedures for designing the
Unit power supply system and I/O power supply system.
*3. Use a voltage that is appropriate for the I/O circuits of the NX Units and the connected external devices.
Refer to the user's manuals for information on the NX Units that can be connected to the NX-series EtherNet/IP Coupler Unit.
Unit | Model |
---|---|
EtherNet/IP Coupler Unit | NX-EIC202 |
Unit | Model | ||||
---|---|---|---|---|---|
2-point Units | 4-point Units | 8-point Units | 16-point Units | 32-point Units | |
Digital Input Unit | - | NX-ID3317
NX-ID3343 NX-ID3417 NX-ID3443 NX-IA3117 |
NX-ID4342
NX-ID4442 |
NX-ID5142-1
NX-ID5142-5 NX-ID5342 NX-ID5442 |
NX-ID6142-5
NX-ID6142-6 NX-ID6342 NX-ID6442 |
Digital Output Unit | NX-OC2633
NX-OC2733 |
NX-OD3121
NX-OD3153 NX-OD3256 NX-OD3257 NX-OD3268 |
NX-OD4121
NX-OD4256 NX-OC4633 |
NX-OD5121
NX-OD5121-1 NX-OD5121-5 NX-OD5256 NX-OD5256-1 NX-OD5256-5 |
NX-OD6121
NX-OD6121-5 NX-OD6121-6 NX-OD6256 NX-OD6256-5 |
Digital Mixed I/O Unit | - | - | - | NX-MD6121-5
NX-MD6121-6 NX-MD6256-5 |
- |
Analog Input Unit | NX-AD2603
NX-AD2604 NX-AD2608 NX-AD2203 NX-AD2204 NX-AD2208 |
NX-AD3603
NX-AD3604 NX-AD3608 NX-AD3203 NX-AD3204 NX-AD3208 |
NX-AD4603
NX-AD4604 NX-AD4608 NX-AD4203 NX-AD4204 NX-AD4208 |
- | - |
Analog Output Unit | NX-DA2603
NX-DA2605 NX-DA2203 NX-DA2205 |
NX-DA3603
NX-DA3605 NX-DA3203 NX-DA3205 |
- | - | - |
Temperature Input Unit | NX-TS2101
NX-TS2102 NX-TS2104 NX-TS2201 NX-TS2202 NX-TS2204 |
NX-TS3101
NX-TS3102 NX-TS3104 NX-TS3201 NX-TS3202 NX-TS3204 |
- | - | - |
Heater Burnout
Detection Unit |
- | NX-HB3101
NX-HB3201 |
- | - | - |
Unit | Model | ||
---|---|---|---|
2CH | 4CH | 8CH | |
Temperature Control Unit | NX-TC2405, NX-TC2406,
NX-TC2407, NX-TC2408 |
NX-TC3405, NX-TC3406, NX-TC3407,
NX-TC3408, NX-HTC3510-5 |
NX-HTC4505-5 |
Unit | Model |
---|---|
Load Cell Input Unit | NX-RS1201 |
Unit | Model | |
---|---|---|
1CH | 2CH | |
Incremental Encoder Input Unit | NX-EC0112, NX-EC0122, NX-EC0132, NX-EC0142 | NX-EC0212, NX-EC0222 |
SSI Input Unit | NX-ECS112 | NX-ECS212 |
Pulse Output Unit | NX-PG0112, NX-PG0122 | - |
Unit | Model |
---|---|
Communications Interface Unit | NX-CIF101, NX-CIF105, NX-CIF210 |
Unit | Model |
---|---|
Additional NX Unit Power Supply Unit | NX-PD1000 |
Additional I/O Power Supply Unit | NX-PF0630, NX-PF0730 |
I/O Power Supply Connection Unit | NX-PC0010, NX-PC0020, NX-PC0030 |
Shield Connection Unit | NX-TBX01 |
Unit | Model |
---|---|
IO-Link Master Unit | NX-ILM400 |
Unit | Model |
---|---|
Safety CPU Unit | NX-SL3300 *1 |
Safety Input Unit | NX-SIH400 *2, NX-SID800 |
Safety Output Unit | NX-SOH200, NX-SOD400 |
*1 Safety CPU Unit Ver.1.1 or higher.
*2 Safety Input Unit Ver.1.1 or higher.
Depending on the type and model of the Unit, some Units do not have all of the versions given in the corresponding versions. If a Unit does not have the specified version, support is provided by the oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and versions.
The versions of each unit and support tool listed in the Corespnding unit version/version indicate whether the EtherNet/IP Coupler Unit can be connected or configured.
EtherNet/IP Coupler Unit | Corresponding unit version/version | ||||
---|---|---|---|---|---|
Model | Unit version | Unit version of
CPU Unit or Industrial PC |
Sysmac Studio
version |
Network Configurator
for EtherNet/IP version |
CX-ConfiguratorFDT
version |
NX-EIC202 | Ver.1.2 | Ver.1.14 | Ver.1.19 | Ver.3.21 | Ver.2.4 * |
Ver.1.0 | Not possible. | Not possible. | Not possible. | Not possible. |
EtherNet/IP Coupler Unit | Corresponding unit version/version | ||||||
---|---|---|---|---|---|---|---|
Model | Unit version | Unit version
of CPU Unit |
Unit version of
CJ1W-EIP21S |
Unit version
of CJ1W-EIP21 |
Sysmac
Studio version |
Network
Configurator for EtherNet/IP version |
CX-
ConfiguratorFDT version |
NX-EIC202 | Ver.1.2 | Ver.1.14 | Ver.1.0
(Lot number 241001[] or later) |
Ver.2.1 | Ver.1.19 | Ver.3.21 | Ver.2.4 * |
Ver.1.0 | Not possible. | Not possible. | Not possible. | Not possible. | Not possible. | Not possible. |
* Final order entry date for CJ1M:The end of March, 2021
EtherNet/IP Coupler Unit | Corresponding unit version/version | ||||||
---|---|---|---|---|---|---|---|
Model | Unit version | Unit version
of CPU Unit |
Unit version of
CS1W-EIP21S |
Unit version
of CS1W-EIP21/ CJ1W-EIP21 |
Network
Configurator for EtherNet/IP version |
NX-IO
Configurator version |
CX-
ConfiguratorFDT version |
NX-EIC202 | Ver.1.2 | Ver.3.0 | Ver.1.0 | Ver.2.1 | Ver.3.00 | Ver.1.00 | Ver.2.4 *1 |
Ver.1.0 | Ver.1.00 *2 | Ver.2.2 |
EtherNet/IP Coupler Unit | Corresponding unit version/version | ||||||
---|---|---|---|---|---|---|---|
Model | Unit version | Unit version
of CPU Unit |
Unit version of
CJ1W-EIP21S |
Unit version
of CJ1W-EIP21 |
Network
Configurator for EtherNet/IP version |
NX-IO
Configurator version |
CX-
ConfiguratorFDT version |
NX-EIC202 | Ver.1.2 | Ver.1.0 | Ver.1.0 | Ver.2.1 | Ver.3.00 | Ver.1.00 | Ver.2.4 *1 |
Ver.1.0 | Ver.1.00 *2 | Ver.2.2 |
EtherNet/IP Coupler Unit | Corresponding unit version/version | ||||||
---|---|---|---|---|---|---|---|
Model | Unit version | Unit version
of CPU Unit |
Unit version of
CJ1W-EIP21S |
Unit version
of CJ1W-EIP21 |
Network
Configurator for EtherNet/IP version |
NX-IO
Configurator version |
CX-
ConfiguratorFDT version |
NX-EIC202 | Ver.1.2 | Ver.1.5 | Ver.1.0 | Ver.2.1 | Ver.3.00 | Ver.1.00 | Ver.2.4 *1 |
Ver.1.0 | Ver.1.00 *2 | Ver.2.2 |
EtherNet/IP Coupler Unit | Corresponding unit version/version | ||||||
---|---|---|---|---|---|---|---|
Model | Unit version | Unit version
of CPU Unit |
Unit version of
CJ1W-EIP21S |
Unit version
of CJ1W-EIP21 |
Network
Configurator for EtherNet/IP version |
NX-IO
Configurator version |
CX-
ConfiguratorFDT version |
NX-EIC202 | Ver.1.2 | Ver.1.0 | Ver.1.0 | Ver.2.1 | Ver.3.21 | Ver.1.00 | Ver.2.4 *1 |
Ver.1.0 | Ver.1.00 *2 | Ver.2.2 |
EtherNet/IP Coupler Unit | Corresponding unit version/version | ||||
---|---|---|---|---|---|
Model | Unit version | Sysmac Gateway
version |
Network Configurator
for EtherNet/IP version |
NX-IO
Configurator version |
CX-
ConfiguratorFDT version |
NX-EIC202 | Ver.1.2 | Ver.1.31 | Ver.3.50 | Ver.1.00 | Ver.2.4 *1 |
Ver.1.0 | Ver.1.00 *2 | Ver.2.2 |
last update: December 16, 2024