Page top

Industrial Automation

Industrial Automation

XW5T-P

DIN Track Push-in Terminal Blocks

XW5T-P

Our Value Design Products Increase the Value of Your Control Panels. Push-in Plus Terminal Blocks to Downsize Control Panels and Save Work.

Ratings and Performance

Ratings

Feed Through Terminal blocks Standard terminals

Model XW5T-P1.5-1.1-1 (BL) XW5T-P2.5-1.1-1 (BL) XW5T-P4.0-1.1-1 (BL)
Appearance and internal
wiring
1 tier, 1:1
3480_sp_1_1
1 tier, 1:1
3480_sp_1_2
1 tier, 1:1
3480_sp_1_3
Appli-
cable
wire
sizes
*1
Stranded wire 0.08 mm2 to 1.5 mm2 0.14 mm2 to 2.5 mm2 0.2 mm2 to 4.0 mm2
Solid wire 0.14 mm2 to 1.5 mm2 0.14 mm2 to 4.0 mm2 0.2 mm2 to 6.0 mm2
Stranded wire
with ferrule
with Plastic
sleeve
0.14 mm2 to 0.75 mm2
(1.5 mm2) *2
0.14 mm2 to 2.5 mm2 0.25 mm2 to 4.0 mm2
Dimensions 3.5 × 45 × 30.5 5.2 × 48.8 × 35.3 6.2 × 56.1 × 35.3
Rated voltage 500 V 800 V
Rated current *3 17.5 A 24 A 32 A
IEC rated voltage 500 V 800 V 800 V
IEC rated current *3 17.5 A/1.5 mm2 24 A/2.5 mm2 32 A/4.0 mm2
Usage Group (UG) B, C D B, C
UL rated voltage 300 V 51-
150 V
151-
300 V
301-
600 V
600 V
UL rated current *3 15 A/
AWG14
(SOL)
10 A/
AWG16
15 A/
AWG14
(SOL)
10 A/
AWG16
10 A/
AWG16
5 A/
AWG
16-20
20 A/AWG12 (SOL),
15 A/AWG14
30 A/AWG10 (SOL),
20 A/AWG12
Dielectric strength 1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA
max.)
2,000 VAC for 1 min
(leakage current: 1 mA
max.)
End Cover XW5E-P1.5-1.1-1 XW5E-P2.5-1.1-1 XW5E-P4.0-1.1-1
Special tool XW4Z-00B XW4Z-00B XW4Z-00B
Applicable nameplates XW5Z-P1.5LB[] or commercially
available nameplate with 9.5 mm
width and 0.5 mm thickness
XW5Z-P2.5LB[] or
commercially available
nameplate with 9.5
mm width and 0.5 mm
thickness
XW5Z-P4.0LB[] or
commercially available
nameplate with 9.5
mm width and 0.5 mm
thickness
Applicable Short Bars XW5S-P1.5-[]
([]: Poles = 2, 3, 4, 5 or 10)
XW5S-P2.5-[]
([]: Poles = 2, 3, 4, 5 or
10)
XW5S-P4.0-[]
([]: Poles = 2, 3, 4, 5 or
10)

*1. For the recommended applicable wire ranges, refer to Data Sheet for solid and stranded wires, and to for ferrules.
*2. You can also use ferrules for 1.0 to 1.5 mm2 wires if you use ferrules without insulation sleeve. Refer to Data Sheet for details.
*3. Do not apply more than the rated current to the terminal block.

Feed Through Terminal blocks Multi tiers terminal

Model XW5T-P1.5-1.1-2 (BL) XW5T-P2.5-1.1-2 (BL) XW5T-P4.0-1.1-2 (BL)
Appearance and internal
wiring
2 tiers, 1:1
3480_sp_2_1
2 tiers, 1:1
3480_sp_2_2
2 tiers, 1:1
3480_sp_2_3
Appli-
cable
wire
sizes
*1
Stranded wire 0.08 mm2 to 1.5 mm2 0.14 mm2 to 2.5 mm2 0.2 mm2 to 4.0 mm2
Solid wire 0.14 mm2 to 1.5 mm2 0.14 mm2 to 4.0 mm2 0.2 mm2 to 6.0 mm2
Stranded wire
with ferrule
with Plastic
sleeve
0.14 mm2 to 0.75 mm2
(1.5 mm2) *2
0.14 mm2 to 2.5 mm2 0.25 mm2 to 4.0 mm2
Dimensions 3.5 × 65.7 × 41.1 5.2 × 78.8 × 45.9 6.2 × 85 × 45.9
Rated voltage 500 V 600 V
Rated current *3 17.5 A 22 A 28 A
IEC rated voltage 500 V
IEC rated current *3 17.5 A/1.5 mm2 22 A/2.5 mm2 28 A/4.0 mm2
Usage Group (UG) B, C D B, C
UL rated voltage 300 V 51-
150 V
151-
300 V
301-
600 V
600 V
UL rated current *3 15 A/
AWG14
(SOL)
10 A/
AWG16
15 A/
AWG14
(SOL)
10 A/
AWG16
10 A/
AWG16
5 A/
AWG
16-20
20 A/AWG12 (SOL),
15 A/AWG14
30 A/AWG10 (SOL),
20 A/AWG12
Dielectric strength 1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA max.)
End Cover XW5E-P1.5-1.1-2 XW5E-P2.5-1.1-2 XW5E-P4.0-1.1-2
Special tool XW4Z-00B
Applicable nameplates XW5Z-P1.5LB2 XW5Z-P2.5LB[] or
commercially available
nameplate with 9.5
mm width and 0.5 mm
thickness
XW5Z-P4.0LB[] or
commercially available
nameplate with 9.5
mm width and 0.5 mm
thickness
Applicable Short Bars XW5S-P1.5-[] 
([]: Poles = 2, 3, 4, 5 or 10)
XW5S-P2.5-[] 
([]: Poles = 2, 3, 4, 5 or
10)
XW5S-P4.0-[] 
([]: Poles = 2, 3, 4, 5 or
10)

*1. For the recommended applicable wire ranges, refer to Data Sheet for solid and stranded wires, and to for ferrules.
*2. You can also use ferrules for 1.0 to 1.5 mm2 wires if you use ferrules without insulation sleeve. Refer to Data Sheet for details.
*3. Do not apply more than the rated current to the terminal block.

Feed Through Terminal blocks Multi conductor terminals

Model XW5T-P1.5-1.2-1 (BL) XW5T-P2.5-1.2-1 (BL) XW5T-P4.0-1.2-1 (BL)
Appearance and internal
wiring
1 tier, 1:2
3480_sp_3_1
1 tier, 1:2
3480_sp_3_2
1 tier, 1:2
3480_sp_3_3
Appli-
cable
wire
sizes
*1
Stranded wire 0.08 mm2 to 1.5 mm2 0.14 mm2 to 2.5 mm2 0.2 mm2 to 4.0 mm2
Solid wire 0.14 mm2 to 1.5 mm2 0.14 mm2 to 4.0 mm2 0.2 mm2 to 6.0 mm2
Stranded wire
with ferrule
with Plastic
sleeve
0.14 mm2 to 0.75 mm2
(1.5 mm2) *2
0.14 mm2 to 2.5 mm2 0.25 mm2 to 4.0 mm2
Dimensions 3.5 × 54.1 × 30.5 5.2 × 60.5 × 35.3 6.2 × 66.5 × 35.3
Rated voltage 500 V 800 V
Rated current *3 17.5 A 24 A 32 A
IEC rated voltage 500 V 800 V
IEC rated current *3 17.5 A/1.5 mm2 24 A/2.5 mm2 32 A/4.0 mm2
Usage Group (UG) B, C D B, C
UL rated voltage 300 V 51-
150 V
151-
300 V
301-
600 V
600 V
UL rated current *3 15 A/
AWG14
(SOL)
10 A/
AWG16
15 A/
AWG14
(SOL)
10 A/
AWG16
10 A/
AWG16
5 A/
AWG
16-20
20 A/AWG12 (SOL),
15 A/AWG14
30 A/AWG10 (SOL),
20 A/AWG12
Dielectric strength 1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA max.)
End Cover XW5E-P1.5-1.2-1 XW5E-P2.5-1.2-1 XW5E-P4.0-1.2-1
Special tool XW4Z-00B
Applicable nameplates XW5Z-P1.5LB[] or commercially
available nameplate with 9.5 mm
width and 0.5 mm thickness
XW5Z-P2.5LB[] or
commercially available
nameplate with 9.5
mm width and 0.5 mm
thickness
XW5Z-P4.0LB[] or
commercially available
nameplate with 9.5
mm width and 0.5 mm
thickness
Applicable Short Bars XW5S-P1.5-[]
([]: Poles = 2, 3, 4, 5 or 10)
XW5S-P2.5-[]
([]: Poles = 2, 3, 4, 5 or
10)
XW5S-P4.0-[]
([]: Poles = 2, 3, 4, 5 or
10)

*1. For the recommended applicable wire ranges, refer to Data Sheet for solid and stranded wires, and to for ferrules.
*2. You can also use ferrules for 1.0 to 1.5 mm2 wires if you use ferrules without insulation sleeve. Refer to Data Sheet for details.
*3. Do not apply more than the rated current to the terminal block.

Model XW5T-P1.5-2.2-1 (BL) XW5T-P2.5-2.2-1 (BL) XW5T-P4.0-2.2-1 (BL)
Appearance and internal
wiring
1 tier, 2:2
3480_sp_4_1
1 tier, 2:2
3480_sp_4_2
1 tier, 2:2
3480_sp_4_3
Appli-
cable
wire
sizes
*1
Stranded wire 0.08 mm2 to 1.5 mm2 0.14 mm2 to 2.5 mm2 0.2 mm2 to 4.0 mm2
Solid wire 0.14 mm2 to 1.5 mm2 0.14 mm2 to 4.0 mm2 0.2 mm2 to 6.0 mm2
Stranded wire
with ferrule
with Plastic
sleeve
0.14 mm2 to 0.75 mm2
(1.5 mm2) *2
0.14 mm2 to 2.5 mm2 0.25 mm2 to 4.0 mm2
Dimensions 3.5 × 63.2 × 30.5 5.2 × 72.2 × 35.3 6.2 × 76.9 × 35.3
Rated voltage 500 V 800 V
Rated current *3 17.5 A 24 A 32 A
IEC rated voltage 500 V 800 V
IEC rated current *3 17.5 A/1.5 mm2 24 A/2.5 mm2 32 A/4.0 mm2
Usage Group (UG) B, C D B, C
UL rated voltage 300 V 51-
150 V
151-
300 V
301-
600 V
600 V
UL rated current *3 15 A/
AWG14
(SOL)
10 A/
AWG16
15 A/
AWG14
(SOL)
10 A/
AWG16
10 A/
AWG16
5 A/
AWG
16-20
20 A/AWG12 (SOL),
15 A/AWG14
30 A/AWG10 (SOL),
20 A/AWG12
Dielectric strength 1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA max.)
End Cover XW5E-P1.5-2.2-1 XW5E-P2.5-2.2-1 XW5E-P4.0-2.2-1
Special tool XW4Z-00B
Applicable nameplates XW5Z-P1.5LB[] or commercially
available nameplate with 9.5 mm
width and 0.5 mm thickness
XW5Z-P2.5LB[] or
commercially available
nameplate with 9.5
mm width and 0.5 mm
thickness
XW5Z-P4.0LB[] or
commercially available
nameplate with 9.5
mm width and 0.5 mm
thickness
Applicable Short Bars XW5S-P1.5-[] 
([]: Poles = 2, 3, 4, 5 or 10)
XW5S-P2.5-[]
([]: Poles = 2, 3, 4, 5 or
10)
XW5S-P4.0-[]
([]: Poles = 2, 3, 4, 5 or
10)

*1. For the recommended applicable wire ranges, refer to Data Sheet for solid and stranded wires, and to for ferrules.
*2. You can also use ferrules for 1.0 to 1.5 mm2 wires if you use ferrules without insulation sleeve. Refer to Data Sheet for details.
*3. Do not apply more than the rated current to the terminal block.

Grounding Terminal blocks Standard terminals

Model XW5G-P1.5-1.1-1 XW5G-P2.5-1.1-1 XW5G-P4.0-1.1-1
Appearance and internal
wiring
1 tier, 1:1
3480_sp_5_1
1 tier, 1:1
3480_sp_5_2
1 tier, 1:1
3480_sp_5_3
Appli-
cable
wire
sizes
*1
Stranded wire 0.08 mm2 to 1.5 mm2 0.14 mm2 to 2.5 mm2 0.2 mm2 to 4.0 mm2
Solid wire 0.14 mm2 to 1.5 mm2 0.14 mm2 to 4.0 mm2 0.2 mm2 to 6.0 mm2
Stranded wire
with ferrule
with Plastic
sleeve
0.14 mm2 to 0.75 mm2
(1.5 mm2) *2
0.14 mm2 to 2.5 mm2 0.25 mm2 to 4.0 mm2
Dimensions 3.5 × 45 × 30.5 5.2 × 48.8 × 35.3 6.2 × 56.1 × 35.3
IEC rated voltage 500 V 800 V
UL rated voltage 600 V
Dielectric strength 1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA max.)
End Cover XW5E-P1.5-1.1-1 XW5E-P2.5-1.1-1 XW5E-P4.0-1.1-1
Special tool XW4Z-00B
Applicable nameplates XW5Z-P1.5LB[] or
commercially available
nameplate with 9.5 mm
width and 0.5 mm
thickness
XW5Z-P2.5LB[] or
commercially available
nameplate with 9.5 mm
width and 0.5 mm
thickness
XW5Z-P4.0LB[] or
commercially available
nameplate with 9.5 mm
width and 0.5 mm
thickness

Note: Use a conductive DIN Track when using a Grounding Terminal Block.
         OMRON does not offer conductive DIN Tracks. Please use a commercially available product.
*1. For the recommended applicable wire ranges, refer to Data Sheet for solid and stranded wires, and to for ferrules.
*2. You can also use ferrules for 1.0 to 1.5 mm2 wires if you use ferrules without insulation sleeve. Refer to Data Sheet for details.

Grounding Terminal blocks Multi tiers terminal

Model XW5G-P1.5-1.1-2 XW5G-P2.5-1.1-2 XW5G-P4.0-1.1-2
Appearance and internal
wiring
2 tier, 1:1
3480_sp_6_1
2 tiers, 1:1
3480_sp_6_2
2 tiers, 1:1
3480_sp_6_3
Appli-
cable
wire
sizes
*1
Stranded wire 0.08 mm2 to 1.5 mm2 0.14 mm2 to 2.5 mm2 0.2 mm2 to 4.0 mm2
Solid wire 0.14 mm2 to 1.5 mm2 0.14 mm2 to 4.0 mm2 0.2 mm2 to 6.0 mm2
Stranded wire
with ferrule
with Plastic
sleeve
0.14 mm2 to 0.75 mm2
(1.5 mm2) *2
0.14 mm2 to 2.5 mm2 0.25 mm2 to 4.0 mm2
Dimensions 3.5 × 65.7 × 41.1 5.2 × 78.8 × 45.9 6.2 × 85 × 45.9
IEC rated voltage 500 V
UL rated voltage 600 V
Dielectric strength 1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA max.)
End Cover XW5E-P1.5-1.1-2 XW5E-P2.5-1.1-2 XW5E-P4.0-1.1-2
Special tool XW4Z-00B
Applicable nameplates XW5Z-P1.5LB2 XW5Z-P2.5LB[] or
commercially available
nameplate with 9.5 mm
width and 0.5 mm
thickness
XW5Z-P4.0LB[] or
commercially available
nameplate with 9.5 mm
width and 0.5 mm
thickness

Note: Use a conductive DIN Track when using a Grounding Terminal Block.
         OMRON does not offer conductive DIN Tracks. Please use a commercially available product.
*1. For the recommended applicable wire ranges, refer to Data Sheet for solid and stranded wires, and to for ferrules.
*2. You can also use ferrules for 1.0 to 1.5 mm2 wires if you use ferrules without insulation sleeve. Refer to Data Sheet for details.

Grounding Terminal blocks Multi conductor terminals

Model XW5G-P1.5-1.2-1 XW5G-P2.5-1.2-1 XW5G-P4.0-1.2-1
Appearance and internal
wiring
1 tier, 1:2
3480_sp_7_1
1 tier, 1:2
3480_sp_7_2
1 tier, 1:2
3480_sp_7_3
Appli-
cable
wire
sizes
*1
Stranded wire 0.08 mm2 to 1.5 mm2 0.14 mm2 to 2.5 mm2 0.2 mm2 to 4.0 mm2
Solid wire 0.14 mm2 to 1.5 mm2 0.14 mm2 to 4.0 mm2 0.2 mm2 to 6.0 mm2
Stranded wire
with ferrule
with Plastic
sleeve
0.14 mm2 to 0.75 mm2
(1.5 mm2) *2
0.14 mm2 to 2.5 mm2 0.25 mm2 to 4.0 mm2
Dimensions 3.5 × 54.1 × 30.5 5.2 × 60.5 × 35.3 6.2 × 66.5 × 35.3
IEC rated voltage 500 V 800 V
UL rated voltage 600 V 600 V
Dielectric strength 1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA max.)
End Cover XW5E-P1.5-1.2-1 XW5E-P2.5-1.2-1 XW5E-P4.0-1.2-1
Special tool XW4Z-00B
Applicable nameplates XW5Z-P1.5LB[] or
commercially available
nameplate with 9.5 mm width
and 0.5 mm thickness
XW5Z-P2.5LB[] or
commercially available
nameplate with 9.5 mm
width and 0.5 mm
thickness
XW5Z-P4.0LB[] or
commercially available
nameplate with 9.5 mm
width and 0.5 mm
thickness

Note: Use a conductive DIN Track when using a Grounding Terminal Block.
         OMRON does not offer conductive DIN Tracks. Please use a commercially available product.
*1. For the recommended applicable wire ranges, refer to Data Sheet for solid and stranded wires, and to for ferrules.
*2. You can also use ferrules for 1.0 to 1.5 mm2 wires if you use ferrules without insulation sleeve. Refer to Data Sheet for details.

Model XW5G-P1.5-2.2-1 XW5G-P2.5-2.2-1 XW5G-P4.0-2.2-1
Appearance and internal
wiring
1 tier, 2:2
3480_sp_8_1
1 tier, 2:2
3480_sp_8_2
1 tier, 2:2
3480_sp_8_3
Appli-
cable
wire
sizes
*1
Stranded wire 0.08 mm2 to 1.5 mm2 0.14 mm2 to 2.5 mm2 0.2 mm2 to 4.0 mm2
Solid wire 0.14 mm2 to 1.5 mm2 0.14 mm2 to 4.0 mm2 0.2 mm2 to 6.0 mm2
Stranded wire
with ferrule
with Plastic
sleeve
0.14 mm2 to 0.75 mm2
(1.5 mm2) *2
0.14 mm2 to 2.5 mm2 0.25 mm2 to 4.0 mm2
Dimensions 3.5 × 63.2 × 30.5 5.2 × 72.2 × 35.3 6.2 × 76.9 × 35.3
IEC rated voltage 500 V 800 V
UL rated voltage 600 V
Dielectric strength 1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA max.)
End Cover XW5E-P1.5-2.2-1 XW5E-P2.5-2.2-1 XW5E-P4.0-2.2-1
Special tool XW4Z-00B
Applicable nameplates XW5Z-P1.5LB[] or
commercially available
nameplate with 9.5 mm width
and 0.5 mm thickness
XW5Z-P2.5LB[] or
commercially available
nameplate with 9.5 mm
width and 0.5 mm
thickness
XW5Z-P4.0LB[] or
commercially available
nameplate with 9.5 mm
width and 0.5 mm
thickness

Note: Use a conductive DIN Track when using a Grounding Terminal Block.
         OMRON does not offer conductive DIN Tracks. Please use a commercially available product.
*1. For the recommended applicable wire ranges, refer to Data Sheet for solid and stranded wires, and to for ferrules.
*2. You can also use ferrules for 1.0 to 1.5 mm2 wires if you use ferrules without insulation sleeve. Refer to Data Sheet for details.

Performance

Operating temperature -40 to 55°C (with no condensation or icing)
Operating humidity 5% to 95%
Insulating material PA resin
Fire resistance UL94 V-0
Insertion durability 50 times
Vibration resistance 10 to 150 Hz, Acceleration of 50 m/s2 for 80 min each in X, Y, and Z directions
Shock resistance 500 m/s2 for 11 ms each in 6 directions 5 times
Storage Temperature Range -40 to 85°C (with no condensation or icing)
Storage Humidity Range 5% to 95%

Short Bars

Model XW5S-P1.5-[] XW5S-P2.5-[] XW5S-P4.0-[]
Rated voltage 500 V 800 V
Rated current 17.5 A 24 A 32 A

Standards

Compliant standard

• UL1059
• CSA (C22.2 No.158)
• IEC 60947-7-1

Certification

• cURus (File No. E245101)