Industrial Switching Hub
            
        
last update: October 1, 2024
| No. of ports (RJ45) | 5 | 
|---|---|
| Ethernet standards | IEEE 802.3 10BASE-T, 100BASE-TX | 
| Auto MDI/MDI-X | Yes | 
| Auto Negotiation | Yes | 
| Store-and-Forward system | Yes | 
| Buffer | 125 KB | 
| Broadcast Storm Detection Function | Yes | 
| QoS for EtherNet/IP | Yes | 
| SNMP | No | 
| VLAN | No | 
| STP | No | 
| IGMP Snooping | No | 
| Port mirroring | No | 
| Current consumption | 70 mA | 
|---|---|
| Power supply voltage | 24 VDC (20.4 to 28.8 VDC) | 
| Power consumption | 1.68 W max. | 
| Wire Type | 0.14 to 1.5 mm2 | 
| Switching capacity
 (Switching fabric) *1  | 
700 Mbps | 
| Ground method | Ground to less than 100 Ω. | 
| Dielectric strength | 1 mA at 250 VAC for 1 minute
 (Between LAN connectors and between FG and power supply connectors)  | 
| EMI and EMS | IEC 61000-6-4
 Conforms to IEC 61000-6-2  | 
| Vibration Resistance | Conforms to IEC 60068-2-6
 5 to 8.4 Hz, 3.5 mm amplitude, 8.4 to 150 Hz, acceleration 9.8 m/s2  | 
| Shock Resistance | Conforms to IEC 60068-2-27
 196 m/s2  | 
| Enclosure | Mounted in a panel | 
| Atmosphere | Must be free from corrosive gases. | 
| Ambient operating
 temperature  | 
0 to 55 °C
 (with no icing or condensation)  | 
| Ambient operating
 humidity  | 
10 % to 95 % (with no condensation) | 
| Ambient storage
 temperature  | 
-20 to 75 °C
 (with no icing or condensation)  | 
| Applicable standards | cULus, EU, RCM, KC | 
*1 Switching capacity per Unit.
last update: October 1, 2024