NX-series EtherNet/IP(TM) Unit
last update: July 3, 2023
Item | Specification | |
---|---|---|
Enclosure | Mounted in a panel | |
Grounding method | Ground to less than 100 Ω. | |
Dimensions: Height × Depth × Width | 100 × 120 × 39 (mm) | |
Weight | 350 g max. | |
Power consumption | 8.1 W max. | |
Operating
environment |
Ambient operating temperature | 0 to 55°C |
Ambient operating humidity | 10% to 95% (with no icing or condensation) | |
Atmosphere | Must be free from corrosive gases. | |
Ambient storage temperature | -25 to 70°C (with no icing or condensation) | |
Altitude | 2,000 m max. | |
Pollution degree | 2 or less: Meets IEC 61010-2-201. | |
Noise immunity | 2 kV on power supply line (Conforms to IEC 61000-4-4.) | |
Overvoltage category | Category II: Meets IEC 61010-2-201. | |
EMC immunity level | Zone B | |
Vibration resistance | Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2 100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) Gravity acceleration is assumed to be G=9.8 m/s2. |
|
Shock resistance | Conforms to IEC 60068-2-27, 147 m/s2, 3 times in X, Y, and Z
directions. Gravity acceleration is assumed to be G=9.8 m/s2. |
|
Mounting method | Mount to DIN Track | |
Mounting direction | One direction (upright) | |
Applicable standards *1 | EU Directives, cULus, RCM, UKCA, KC |
*1. Consult your OMRON representative for the most recent applicable standards for each model.
Item | NX-EIP201 | |||
---|---|---|---|---|
EtherNet/IP
port |
Number of ports | 2 | ||
Physical layer | 10BASE-T, 100BASE-TX, or 1000BASE-T | |||
Frame length | 1,514 bytes max. | |||
Media access method | CSMA/CD | |||
Modulation | Baseband | |||
Topology | Star | |||
Baud rate | 1 Gbps (1000BASE-T) max. | |||
Transmission media | STP (shielded, twisted-pair) cable of Ethernet category
5, 5e or higher |
|||
Maximum transmission distance between
Ethernet switch and node |
100 m | |||
Maximum number of cascade connections | There are no restrictions if an Ethernet switch is used. | |||
LLDP | Supported. | |||
BOOTP client | Supported. | |||
DNS client | Supported. | |||
SNMP agent, traps | Supported. | |||
CIP
service: Tag data links (cyclic commu- nications) |
Maximum number of connections | 256 per port
512 total |
||
Packet interval *1, *2 | Can be set for each connection.
1.0 to 10,000 ms in 1-ms increments |
|||
Allowed communications
bandwidth per Unit |
40,000 pps *3, *4 (including heartbeat) | |||
Maximum number of tag sets | 256 per port
512 total |
|||
Tag types | Network variables
CIO, Work, Holding, DM, or EM Areas can be used. |
|||
Number of tags per connection
(i.e., per tag set) |
64 (63 tags if Controller status is included in the tag
set.) |
|||
Maximum number of tags | 1,024 per port
2,048 total |
|||
Maximum link data size per node
(total size for all tags) |
369,664 bytes per port (total of 739,328 bytes with two
ports) |
|||
Maximum data size per
connection |
1,444 bytes | |||
Maximum number of registrable
tag sets |
256 per port
512 total (1 connection = 1 tag set) |
|||
Maximum tag set size | 1,444 bytes (Two bytes are used if Controller status is
included in the tag set.) |
|||
Multicast packet filter *5 | Supported. | |||
CIP
message service: Explicit messages |
Class 3 (number of connections) | 128 per port
256 total (clients plus server) |
||
UCMM
(non- connection type) |
Maximum number of
clients that can communicate at one time |
32 per port
64 total |
||
Maximum number of
servers that can communicate at one time |
32 per port
64 total |
|||
CIP Safety
routing *6 |
Maximum number of routable CIP
Safety connections |
84 total
(originator: 80, target: 4) |
||
Maximum routable safety data
length per connection |
32 bytes | |||
SNMP | Agents | SNMPv1, SNMPv2C | ||
MIB | MIB-II | |||
EtherNet/IP conformance test | Conforms to CT18. | |||
Ethernet interface | 10BASE-T, 100BASE-TX, or 1000BASE-T
Auto negotiation |
Item | NX-EIP201 | |||
---|---|---|---|---|
Communi-
cations |
EtherNet/IP
port |
Communications protocol | TCP/IP or UDP/IP | |
CIP commu-
nications services |
Tag data links | Programless cyclic data exchange is performed with
the devices on the EtherNet/IP network. |
||
Message
Communications |
CIP commands are sent to or received from the
devices on the EtherNet/IP network. |
|||
TCP/IP
application |
SNMP agent | EtherNet/IP port internal status information is
provided to network management software that uses an SNMP manager. |
||
System
management |
Event logs | Function | Events are recorded in the logs. | |
Maximum
number of events |
System event log | 1,024 | ||
Access event log | 512 | |||
User-defined
event log |
None |
NX-EIP201 | Sysmac Studio | Network Configurator *1 |
---|---|---|
Ver.1.0 | Ver.1.54 or higher | Ver.3.74 or higher |
*1. This software is used to configure tag data links.
last update: July 3, 2023