Page top

Industrial Automation

Industrial Automation

K8DT-AW

Single-phase Overcurrent/Undercurrent Relay

K8DT-AW

Our Value Design Products Increase the Value of Your Control Panels. Detect errors in motors and other equipment through current changes. Monitor for overcurrents and undercurrents simultaneously with one Relay.

Single-phase Overcurrent/Undercurrent Relay

Setting range Power supply voltage Output Model
2 to 20 mA AC/DC
10 to 100 mA AC/DC
50 to 500 mA AC/DC
24 VAC/DC Relay: SPDT contact output K8DT-AW1CD
Transistor K8DT-AW1TD
100 to 240 VAC Relay: SPDT contact output K8DT-AW1CA
Transistor K8DT-AW1TA
0.1 to 1 A AC/DC
0.5 to 5 A AC/DC
24 VAC/DC Relay: SPDT contact output K8DT-AW2CD
Transistor K8DT-AW2TD
100 to 240 VAC Relay: SPDT contact output K8DT-AW2CA
Transistor K8DT-AW2TA
10 to 100 A AC *
20 to 200 A AC *
24 VAC/DC Relay: SPDT contact output K8DT-AW3CD
Transistor K8DT-AW3TD
100 to 240 VAC Relay: SPDT contact output K8DT-AW3CA
Transistor K8DT-AW3TA

* The K8DT-AW3[][] is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.)

OMRON CT

Appearance Input range Applicable Relay Model
3492_lu_2_1 10 to 100 A AC,
20 to 200 A AC
K8DT-AW3 K8AC-CT200L

Commercially Available CTs *

Appearance CT current on secondary side Applicable Relay
3492_lu_3_1 0 to 1 A AC,
0 to 5 A AC
K8DT-AW2

* If you use a commercially available CT, do not exceed the overload capacity of the K8DT-AW2.

Options (Order Separately)

Front Cover

Appearance Model
3492_lu_4_1 Y92A-D1A