Single-phase Overvoltage/Undervoltage Relay
last update: March 1, 2019
Model | Range * | Connection terminal | Setting range | Input impedance | Overload capacity |
---|---|---|---|---|---|
K8AK-VW2[][] | 0 to 10 V AC/DC | V1-COM | 1 to 10 V AC/DC | Approx. 120 kΩ | Continuous input at 115% of
maximum input. 10 s at 125% (up to 600 VAC) |
0 to 30 V AC/DC | V2-COM | 3 to 30 V AC/DC | Approx. 320 kΩ | ||
0 to 150 V AC/DC | V3-COM | 15 to 150 V AC/DC | Approx. 1.6 MΩ | ||
K8AK-VW3[][] | 0 to 200 V AC/DC | V1-COM | 20 to 200 V AC/DC | Approx. 1.2 MΩ | |
0 to 300 V AC/DC | V2-COM | 30 to 300 V AC/DC | Approx. 1.7 MΩ | ||
0 to 600 V AC/DC | V3-COM | 60 to 600 V AC/DC | Approx. 3.1 MΩ |
* The range is selected using connected terminals.
Power supply
voltage |
K8DT-VW[][]D: 24 VAC 50/60 Hz, 24 VDC
K8DT-VW[][]A: 100 to 240 VAC 50/60 Hz |
---|---|
Power consumption | 24 VAC/DC: 1.8 VA/1 W max.
100 to 240 VAC: 2.5 VA max. |
Rated insulation
voltage |
600 VAC |
Operating value setting
range (AL1 and AL2) |
10% to 100% of the maximum value of the setting range
K8DT-VW2: 1 to 10 V AC/DC 3 to 30 V AC/DC 15 to 150 V AC/DC K8DT-VW3: 20 to 200 V AC/DC 30 to 300 V AC/DC 60 to 600 V AC/DC |
Operating value | 100% operation at set value |
Reset value | 5% of operating value (fixed) |
Reset method | Manual reset/automatic reset (switchable)
Manual reset: Turn OFF power supply for 1 s or longer. |
Operating time
setting range (T) |
0.1 to 30 s |
Power ON lock time | 1 s or 5 s (Switched using DIP switch.) |
Indicators | Power (PWR): Green, Relay output (RY): Yellow,
Alarm output1 (AL1): Red, Alarm output2 (AL2): Red |
Input impedance | Refer to Input Range on catalog. |
Output form | Relay Output: SPDT contact
Transistor Output: 1 |
Output relay ratings | Rated load
5 A at 250 VAC (Resistive load) 5 A at 30 VDC (Resistive load) 1 A at 250 VAC (Inductive load) 0.2 A at 48 VDC (Inductive load) Minimum load: 5 VDC, 10 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC or 30 VDC: 100,000 operations |
Transistor output
ratings |
Rated voltage: 24 VDC (maximum voltage: 26.4 VDC)
Maximum current: 50 mA DC |
Ambient operating
temperature |
-20 to 60°C (with no condensation or icing) |
Storage temperature | -25 to 65°C (with no condensation or icing) |
Ambient operating
humidity |
25% to 85% RH (with no condensation) |
Storage humidity | 25% to 85% RH (with no condensation) |
Altitude | 2,000 m max. |
Applicable wires | Stranded wires, solid wires, or ferrules |
Applicable wire size | 0.25 to 1.5 mm2(AWG24 to AWG16) |
Wire insertion force | 8 N max. for AWG20 wire |
Screwdriver
insertion force |
15 N max. |
Wire stripping length | 8 mm |
Ferrule length | 8 mm |
Recommended flat-blade screwdriver | XW4Z-00B (Omron)
SZF 0.4 ×2.5 (Phoenix Contact) 210-719 (Wago) SDI 0.4 ×2.5 ×75 (Weidmuller) |
Current capacity | 10 A (per pole) |
Number of insertions | 50 times |
Case color | N1.5 |
Case material | PC, UL 94 V-0 |
Weight | Approx. 100 g |
Mounting | Mounts to DIN Track, or screw mounting |
Dimensions | 17.5 × 90 × 90 mm (W×H×D) |
Allowable operating
voltage range |
85% to 110% of rated power supply voltage | |
---|---|---|
Allowable operating
frequency range |
50/60 Hz ±5 Hz | |
Input frequency range | 40 to 500 Hz | |
Overload capacity | Continuous input at 115% of maximum input, 10 s at 125% (up to 600 VAC). | |
Repeat
accuracy |
Operating
value |
±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage) |
Operating
time |
±50 ms (at 25°C and 65% humidity, rated power supply voltage) | |
Applicable
standards |
Conforming
standards |
EN 60947-5-1
Installation environment (pollution level 2, Overvoltage category III) |
EMC | EN 60947-5-1 | |
Safety
standards |
UL 60947-5-1 (Listing),
Korean Radio Waves Act (Act 10564), CCC (GB/T 14048.5) |
|
Insulation resistance | 20 MΩmin.
Between all external terminals and the case Between all power supply terminals and all input terminals Between all power supply terminals and all output terminals Between all input terminals and all output terminals |
|
Dielectric strength | 2,000 VAC for 1 min
Between all external terminals and the case Between all power supply terminals and all input terminals Between all power supply terminals and all output terminals Between all input terminals and all output terminals |
|
Impulse withstand
voltage |
6 kV (between live terminals and exposed, non-charged metal parts) | |
Noise immunity | Square-wave noise of 1 μs/100-ns pulse width with 1-ns rise time
100 to 240 VAC: 1,500 V power supply terminal common/normal mode 24 VAC: 1,500 V power supply terminal common/normal mode 24 VDC: 480 V power supply terminal common |
|
Vibration resistance | Frequency: 10 to 55 Hz, 0.35-mm single amplitude
10 sweeps of 5 min each in X,Y, and Z directions |
|
Shock resistance | 100 m/s2, 3 times each in 6 directions along 3 axes | |
Degree of protection | Terminals: IP20 |