Conductive Level Controller
last update: March 1, 2019
Power supply voltage | K8DT-LS1[]D: 24 VAC 50/60 Hz, 24 VDC
K8DT-LS1[]A: 100 to 240 VAC 50/60 Hz |
---|---|
Voltage across
electrodes |
5 V p-p (Approx. 20 Hz) |
Power consumption | 24 VAC/DC: 1.8 VA/1 W max.
100 to 240 VAC: 2.5 VA max. |
Rated insulation
voltage |
253 VAC |
Operating resistance | 10 to 100 kΩ (variable) |
Reset resistance | 250 kΩ max. |
Response time | Approx. 0.1 to 10 s (variable) |
Length of cable | 100 m max.
(fully insulated 3-core 0.75-mm2 cabtyre cable, 600 V) |
Indicators | power PWR: Green, output (OUT): Yellow |
Output form | Relay Output: SPDT contact
Transistor Output: 1 |
Output contact ratings | Rated load
5 A at 250 VAC (Resistive load) 5 A at 30 VDC (Resistive load) 1 A at 250 VAC (Inductive load) 0.2 A at 48 VDC (Inductive load) Minimum load: 5 VDC, 10 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC or 30 VDC: 100,000 operations |
Transistor output
ratings |
Rated voltage: 24 VDC (maximum voltage: 26.4 VDC)
Maximum current: 50 mA DC |
Ambient operating
temperature |
-20 to 60°C (with no condensation or icing) |
Storage temperature | -25 to 65°C (with no condensation or icing) |
Ambient humidity | 25% to 85% RH (with no condensation) |
Storage humidity | 25% to 85% RH (with no condensation) |
Altitude | 2,000 m max. |
Applicable wires | Stranded wires, solid wires, or ferrules |
Applicable wire size | 0.25 to 1.5 mm2 (AWG24 to AWG16) |
Wire insertion force | 8 N max. for AWG20 wire |
Screwdriver insertion
force |
15 N |
Wire stripping length | 8 mm |
Ferrule length | 8 mm |
Recommended flatblade
screwdriver |
XW4Z-00B (Omron)
SZF 0.4 × 2.5 (Phoenix Contact) 210-719 (Wago) SDI 0.4 × 2.5 × 75 (Weidmuller) |
Current capacity | 10 A (per pole) |
Number of insertions | 50 times |
Case color | N1.5 |
Case material | PC, UL 94 V-0 |
Weight | Approx. 100 g |
Mounting | Mounts to DIN Track, or screw mounting |
Dimensions | 17.5 × 90 × 90 mm (W×D×H) |
Operating voltage
range |
85% to 110% of rated voltage | |
---|---|---|
Applicable
standards |
Approved
standards |
EN 61010-1
Installation environment: pollution level 2, Overvoltage category II |
EMC | EN 61326-1 *1 | |
Safety
standards |
UL 61010-1 (Listing)
Korean Radio Waves Act (Act 10564), CCC (GB/T 14048.5) *2 |
|
Insulation resistance | 20 MΩ min.
Between all external terminals and the case Between all power supply terminals and all input terminals Between all power supply terminals and all output terminals Between all input terminals and all output terminals |
|
Dielectric strength | 3,000 VAC for 1 min
Between all external terminals and the case Between all power supply terminals and all input terminals Between all power supply terminals and all output terminals Between all input terminals and all output terminals |
|
Impulse withstand
voltage |
6 kV (between live terminals and exposed, non-charged metal parts) | |
Noise immunity | Square-wave noise of 1-μs/100-ns pulse width with 1-ns rise time
100 to 240 VAC: 1,500 V power supply terminal common/normal mode 24 VAC: 1,500 V power supply terminal common/normal mode 24 VDC: 480 V power supply terminal common |
|
Vibration resistance | Frequency: 10 to 55 Hz, 0.35-mm single amplitude
10 sweeps of 5 min each in X,Y, and Z directions |
|
Shock resistance | 100 m/s2, 3 times each in 6 directions along 3 axes | |
Degree of protection | Terminals: IP20 |
*1. Industrial Electromagnetic Environment (EN/IEC 61326-1, Table 2)
*2. K8DT-LS1TD is not applied.
last update: March 1, 2019