Three-phase Voltage, Asymmetry, and Phase-sequence Phase-loss Relay
             
        
last update: March 1, 2019
| Rated input voltage | K8DT-PZ1[]N: Three-phase, three-wire Mode: 200, 220, 230, or 240 VAC K8DT-PZ2[]N: Three-phase, three-wire Mode: 380, 400, 415, or 480 VAC | |
|---|---|---|
| Input load | K8DT-PZ1: Approx. 1.7 VA K8DT-PZ2: Approx. 2.7 VA | |
| Rated insulation voltage | 528 VAC | |
| Operating value setting range | Overvoltage/Undervoltage 2% to 30% of rated input voltage Asymmetry 5% to 22% of rated input voltage Note: The rated input voltage can be switched by using the DIP switches. | |
| Operating value | Overvoltage/Undervoltage Operates at 100% of set value. Asymmetry Asymmetry operating value = Rated input voltage × Asymmetry set value (%) The asymmetry operation will function when the potential difference between the highest and lowest voltage phases equals or exceeds the asymmetry operating value. | |
| Reset value | 2% of operating value (fixed) | |
| Reset method | Automatic reset | |
| Operating time setting range | Overvoltage/ Undervoltage | 0.1 to 30 s | 
| Asymmetry | 0.1 to 30 s | |
| Phase sequence | 0.1 s±0.05 s | |
| Phase loss | 0.1 s max. | |
| Power ON lock time (LOCK) | 1 s/5 s (switched by using the DIP switch) | |
| Indicators | Power (PWR): Green, Output (OUT): Yellow, Alarm outputs (ALM): Red | |
| Output form | Relay Output: SPDT contact Transistor Output: 1 | |
| Output relay ratings | Rated load 5 A at 250 VAC (Resistive load) 5 A at 30 VDC (Resistive load) 1 A at 250 VAC (Inductive load) 0.2 A at 48 VDC (Inductive load) Minimum load: 5 VDC, 10 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC or 30 VDC: 100,000 operations | |
| Transistor output ratings | Rated voltage: 24 VDC (maximum voltage: 26.4 VDC) Maximum current: 50 mA DC | |
| Ambient operating temperature | -20 to 60°C (with no condensation or icing) | |
| Storage temperature | -25 to 65°C (with no condensation or icing) | |
| Ambient operating humidity | 25% to 85% RH (with no condensation) | |
| Storage humidity | 25% to 85% RH (with no condensation) | |
| Altitude | 2,000 m max. | |
| Applicable wires | Stranded wires, solid wires, or ferrules | |
| Applicable wire size | 0.25 to 1.5 mm2 (AWG24 to AWG16) | |
| Wire insertion force | 8 N max. for AWG20 wire | |
| Screwdriver insertion force | 15 N max. | |
| Wire stripping length | 8 mm | |
| Ferrule length | 8 mm | |
| Recommended flatblade screwdriver | XW4Z-00B (Omron) SZF 0.4 × 2.5 (Phoenix Contact) 210-719 (Wago) SDI 0.4 × 2.5 × 75 (Weidmuller) | |
| Current capacity | 10 A (per pole) | |
| Number of insertions | 50 times | |
| Case color | N1.5 | |
| Case material | PC, UL 94 V-0 | |
| Weight | Approx. 100 g | |
| Mounting | Mounts to DIN Track, or screw mounting | |
| Dimensions | 17.5 × 90 × 90 mm (W×D×H) | |
| Input frequency | 50/60 Hz | |
|---|---|---|
| Overload capacity | Continuous 528 V | |
| Repeat accuracy | Operating value | ±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage) | 
| Operating time | ±50 ms (at 25°C and 65% humidity, rated power supply voltage) | |
| Applicable standards | Conforming standards | EN 60947-5-1 Installation environment (pollution level 2, Overvoltage category III) | 
| EMC | EN 60947-5-1 | |
| Safety standards | UL 60947-5-1 (Listing), Korean Radio Waves Act (Act 10564), CCC (GB/T 14048.5), LR (Category ENV1.2) | |
| Insulation resistance | 20 MΩ min. Between external terminals and case Between input terminals and output terminals | |
| Dielectric strength | 2,000 VAC for one minute Between external terminals and case Between input terminals and output terminals | |
| Impulse withstand voltage | 6 kV (between live terminals and exposed, noncharged metal parts) | |
| Noise immunity | 1,500 V power supply terminal common/normal mode Square-wave noise of 1 μs/100 ns pulse width with 1-ns rise time | |
| Vibration resistance | Frequency: 10 to 55 Hz, 0.35-mm single amplitude 10 sweeps of 5 min each in X,Y, and Z directions | |
| Shock resistance | 100 m/s2, 3 times each in 6 directions along 3 axes | |
| Degree of protection | Terminals: IP20 | |