Basic-type Digital Temperature Controller (48 x 24 mm)
last update: August 6, 2015
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC |
|
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power
consump- tion |
E5GN
Screw terminal block |
100 to 240 VAC: 5.5 VA (max.)
24 VAC/VDC: 3 VA/2 W (max.) |
E5GN-[]-C
Screwless clamp terminal block |
100 to 240 VAC: 5.5 VA (max.)
24 VAC/VDC: 3 VA/2 W (max.) |
|
Sensor input | Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Voltage input: 0 to 50 mV |
|
Models with analog inputs
Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V |
||
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control
outputs |
Relay output | SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
10 mA |
Voltage output
(for driving SSR) |
Output voltage: 12 VDC ± 15% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary
outputs |
Number of outputs | 1 or 2 max. (Depends on the model.) |
Output
specifications |
Relay output: SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum
applicable load: 5 V, 10 mA |
|
Event
inputs |
Number of inputs | 2 |
External contact
input specifications |
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Setting method | Digital setting using front panel keys | |
Indication method | 11-segment digital display and individual indicators (7-segment display also possible)
Character height: PV: 7.5 mm, SV: 3.6 mm |
|
Multi SP | Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial
communications. |
|
Bank switching | Not supported | |
Other functions | Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
detection (including SSR failure and heater over current detection), 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic operations, PV/SV status display, simple program, automatic cooling coefficient adjustment |
|
Ambient operating temperature | -10 to 55 °C (with no condensation or icing), for 3-year warranty: -10 to 50 °C | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65 °C (with no condensation or icing) |
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
Input Type | Current | Voltage | |||
---|---|---|---|---|---|
Input specification | 4 to 20 mA | 0 to 20 mA | 1 to 5 V | 0 to 5 V | 0 to 10 V |
Setting range | Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 |
||||
Setting number | 0 | 1 | 2 | 3 | 4 |
Shaded settings are the default settings.
Set
value |
Alarm type | Alarm output operation | Description of function | |
---|---|---|---|---|
When alarm value
X is positive |
When alarm value
X is negative |
|||
0 | Alarm function OFF | Output OFF | No alarm | |
1 *1 | Upper- and lower-limit | ![]() |
*2 | Set the deviation in the set point by
setting the alarm upper limit (H) and alarm lower limit (L). |
2 | Upper-limit | ![]() |
![]() |
Set the upward deviation in the set point
by setting the alarm value (X). |
3 | Lower-limit | ![]() |
![]() |
Set the downward deviation in the set
point by setting the alarm value (X). |
4 *1 | Upper- and lower-limit
range |
![]() |
*3 | Set the deviation in the set point by
setting the alarm upper limit (H) and alarm lower limit (L). |
5 *1 | Upper- and lower-limit with
standby sequence |
![]() |
*4 | A standby sequence is added to the
upper- and lower-limit alarm (1). *6 |
6 | Upper-limit with standby
sequence |
![]() |
![]() |
A standby sequence is added to the
upper-limit alarm (2). *6 |
7 | Lower-limit with standby
sequence |
![]() |
![]() |
A standby sequence is added to the
lower-limit alarm (3). *6 |
8 | Absolute-value upper-limit | ![]() |
![]() |
The alarm will turn ON if the process
value is larger than the alarm value (X) regardless of the set point. |
9 | Absolute-value lower-limit | ![]() |
![]() |
The alarm will turn ON if the process
value is smaller than the alarm value (X) regardless of the set point. |
10 | Absolute-value upper-limit
with standby sequence |
![]() |
![]() |
A standby sequence is added to the
absolute-value upper- limit alarm (8). *6 |
11 | Absolute-value lower-limit
with standby sequence |
![]() |
![]() |
A standby sequence is added to the
absolute-value lower-limit alarm (9). *6 |
12 | LBA (alarm 1 type only) | --- | Refer to Data Sheet. | |
13 | PV change rate alarm | --- | Refer to Data Sheet. |
*3. Set value: 4, Upper- and lower-limit range
Indication accuracy | Thermocouple: *1
(± 0.3% of indicated value or ± 1 °C, whichever is greater) ± 1 digit max. Platinum resistance thermometer input: (± 0.2% of indicated value or ± 0.8 °C, whichever is greater) ± 1 digit max. Analog input: ± 0.2% FS ± 1 digit max. CT input: ± 5% FS ± 1 digit max. |
|
---|---|---|
Influence of temperature
*2 |
Thermocouple input (R, S, B, W, PL II):
(± 1% of PV or ± 10 °C, whichever is greater) ± 1 digit max. Other thermocouple input: *3 (± 1% of PV or ± 4 °C, whichever is greater) ± 1 digit max. Platinum resistance thermometer input: (± 1% of PV or ± 2 °C, whichever is greater) ± 1 digit max. Analog input: (± 1%FS) ± 1 digit max. |
|
Influence of voltage *2 | ||
Influence of EMS.
(at EN 61326-1) |
||
Input sampling period | 250 ms | |
Hysteresis | Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS) |
|
Proportional band (P) | Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS) |
|
Integral time (I) | 0 to 3999 s (in units of 1 s) | |
Derivative time (D) | 0 to 3999 s (in units of 1 s) *5 | |
Control period | 0.5, 1 to 99 s (in units of 1 s) | |
Manual reset value | 0.0 to 100.0% (in units of 0.1%) | |
Alarm setting range | -1999 to 9999 (decimal point position depends on input type) | |
Affect of signal source
resistance |
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) |
|
Insulation resistance | 20 MΩ min. (at 500 VDC) | |
Dielectric strength | 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) | |
Vibration
resistance |
Malfunction | 10 to 55 Hz, 20 2 for 10 min each in X, Y, and Z directions |
Destruction | 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions | |
Shock
resistance |
Malfunction | 100 2, 3 times each in X, Y, and Z directions |
Destruction | 300 2, 3 times each in X, Y, and Z directions | |
Weight | Controller: Approx. 90 g, Mounting Bracket: Approx. 10 g | |
Degree of protection | Front panel: IP66, Rear case: IP20, Terminals: IP00 | |
Memory protection | Non-volatile memory (number of writes: 1,000,000 times) | |
Setup Tool | CX-Thermo version 4.2 or higher | |
Setup Tool port | Provided on the side of the E5GN. Connect this port to the computer when using the Setup Tool. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the port on the side of the E5GN. *6 | |
Standards | Approved
standards |
UL 61010-1, CSA C22.2 No. 1010-1 |
Conformed
standards |
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II | |
EMC | EMI: EN 61326-1 *7
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326-1 *7 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Power Frequency Magnetic Field Immunity: EN 61000-4-8 Voltage Dip/Interrupting Immunity: EN 61000-4-11 |
Applicable OS | Windows XP/Vista/7/8 |
---|---|
Applicable software | CX-Thermo version 4 or higher |
Applicable models | E5AN/E5EN/E5CN/E5CN-U/E5AN-H/E5EN-H/E5CN-H/E5GN |
USB interface standard | Conforms to USB Specification 1.1. |
DTE speed | 38400 bps |
Connector specifications | Computer: USB (type A plug)
Temperature Controller: Setup Tool port (on bottom of Controller) |
Power supply | Bus power (Supplied from USB host controller.) |
Power supply voltage | 5 VDC |
Current consumption | 70 mA |
Ambient operating temperature | 0 to 55°C (with no condensation or icing) |
Ambient operating humidity | 10% to 80% |
Storage temperature | - 20 to 60°C (with no condensation or icing) |
Storage humidity | 10% to 80% |
Altitude | 2,000 m max. |
Weight | Approx. 100 g |
Transmission line connection method | RS-485: Multipoint RS-232C: Point-to-point |
---|---|
Communications | RS-485 (two-wire, half duplex), RS-232C |
Synchronization method | Start-stop synchronization |
Protocol | CompoWay/F, SYSWAY, or Modbus |
Baud rate | 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps |
Transmission code | ASCII |
Data bit length * | 7 or 8 bits |
Stop bit length * | 1 or 2 bits |
Error detection | Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus |
Flow control | None |
Interface | RS-485, RS-232C |
Retry function | None |
Communications buffer | 217 bytes |
Communications response wait time | 0 to 99 ms Default: 20 ms |
Dielectric strength | 1,000 VAC for 1 min |
---|---|
Vibration resistance | 50 Hz, 98 m/s2 |
Weight | E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g |
Accessories (E54-CT3 only) | Armatures (2) Plugs (2) |
CT input (for heater current detection) | Models with detection for single-phase heaters: One input |
---|---|
Maximum heater current | 50 A AC |
Input current indication accuracy | ±5% FS ±1 digit max. |
Heater burnout alarm setting range *1 | 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms |
SSR failure alarm setting range *2 | 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms |
Heater overcurrent alarm setting range *3 | 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms |
last update: August 6, 2015